Goodman Mfg GKS9 User Manual

Page 33

Advertising
background image

33

To remove filters from an external filter rack in an upright upflow
installation, follow the directions provided with external filter rack
kit. For further details, see your distributor.

H

ORIZONTAL

U

NIT

F

ILTER

R

EMOVAL

Filters in horizontal installations are located in the central return
register or the ductwork near the furnace.

To remove:

1. Turn OFF electrical power to furnace.
2. Remove filter(s) from the central return register or ductwork.
3. Replace filter(s) by reversing the procedure for removal.
4. Turn ON electrical power to furnace.

M

EDIA

A

IR

F

ILTER

OR

E

LECTRONIC

A

IR

C

LEANER

R

EMOVAL

Follow the manufacturer’s directions for service.

B

URNERS

Visually inspect the burner flames periodically during the heating
season. Turn on the furnace at the thermostat and allow several
minutes for flames to stabilize, since any dislodged dust will alter
the flames normal appearance. Flames should be stable, quiet,
soft, and blue (dust may cause orange tips but they must not be
yellow). They should extend directly outward from the burners with-
out curling, floating, or lifting off. Flames must not impinge on the
sides of the heat exchanger firing tubes.

I

NDUCED

D

RAFT

AND

C

IRCULATOR

B

LOWERS

The bearings in the induced draft blower and circulator blower
motors are permanently lubricated by the manufacturer. No further
lubrication is required. Check motor windings for accumulation of
dust which may cause overheating. Clean as necessary.

C

ONDENSATE

T

RAP

AND

D

RAIN

S

YSTEM

(Q

UALIFIED

S

ERVICER

O

NLY

)

Annually inspect the drain tubes, drain trap, and field-supplied drain
line for proper condensate drainage. Check drain system for hose
connection tightness, blockage, and leaks. Clean or repair as
necessary.

F

LAME

S

ENSOR

(Q

UALIFIED

S

ERVICER

O

NLY

)

Under some conditions, the fuel or air supply can create a nearly
invisible coating on the flame sensor. This coating acts as an
insulator causing a drop in the flame sense signal. If the flame
sense signal drops too low the furnace will not sense flame and
will lock out. The flame sensor should be carefully cleaned by a
qualified servicer using emery cloth or steel wool. Following clean-
ing, the flame sense signal should be 1 to 6 microamps.

I

GNITER

(Q

UALIFIED

S

ERVICER

O

NLY

)

If the igniter and the surrounding air are at about 70°F and the
igniter wires are not connected to any other electrical components,
the resistance of the igniter should not exceed 200 ohms. If it does,
the igniter should be replaced.

F

LUE

P

ASSAGES

(Q

UALIFIED

S

ERVICER

O

NLY

)

The heat exchanger flue passageways should be inspected at the
beginning of each heating season. If necessary, clean the pas-
sageways as outlined below.

1. Turn OFF the electrical power and gas supply to the furnace.
2. Disconnect the gas line and remove the burner/ manifold

assembly by removing the screws securing the assembly
to the partition panel.

3. Disconnect the flue pipe system from the induced draft

blower.

4. Remove the induced draft blower and the drain and pressure

tap hoses from the recuperator coil front cover.

5. Remove the recuperator coil front cover to expose the coil

tubes and turbulators.

6. Remove the recuperator coil turbulators individually by slowly

pulling each turbulator forward firmly.

7. Clean the recuperator coil tubes using a long handle wire

brush, such as a gun cleaning brush.

8. Clean the primary heat exchanger tubes using a wire brush

attached to a length of high grade stainless steel cable,
such as drain cleanout cable. Attach a variable speed
reversible drill to the other end of the cable. Slowly rotate
the cable with the drill and insert it into one of the heat
exchanger tubes. While reversing the drill, work the cable
in and out several times to obtain sufficient cleaning. Repeat
for each tube.

9. Clean residue from furnace using a vacuum cleaner.
10. Replace the parts removed in the previous steps in reverse

order.

11. Turn on electrical power and gas to furnace. Check for

leaks and proper unit operation.

12. Severe heat exchanger fouling is an indication of an

operational problem. Perform the checks listed in Section
XIV, Startup Procedure and Adjustments
to reduce the
chances of repeated fouling.

XX. BEFORE LEAVING AN INSTALLATION

Cycle the furnace with the thermostat at least three times.
Verify cooling and fan only operation.

Review the Owner’s Manual with the homeowner and
discuss proper furnace operation and maintenance.

Leave literature packet near furnace.

XXI. REPAIR & REPLACEMENT PARTS

When ordering any of the listed functional parts, be sure to
provide the furnace model, manufacturing, and serial
numbers with the order.

Although only functional parts are shown in the parts list, all
sheet metal parts, doors, etc. may be ordered by description.

Parts are available from your distributor.

Functional Parts List-

Gas Valve

Blower Motor

Gas Manifold

Blower Wheel

Natural Gas Orifice

Blower Mounting Bracket

Propane Gas Orifice

Blower Cutoff

Igniter

Blower Housing

Flame Sensor

Capacitor

Rollout Limit Switch

Heat Exchanger

Primary Limit Switch

Recuperator Coil

Auxiliary Limit Switch

Coil Front Cover

Pressure Switch

Integrated Control Module

Induced Draft Blower

Transformer

Door Switch

Advertising