Electrical wiring (milli-volt) – MartinLogan VENT-FREE FIREPLACE SYSTEMS 33ISDG User Manual

Page 20

Advertising
background image

20

23D8036

ELECTRICAL WIRING (MILLI-VOLT)

A. COMPLETE MILLIVOLT SYSTEM CHECK

(“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should turn ON)

a. If the reading is more than 100 milli-volts and the automatic valve still does not come on, replace the control.

b. If the closed circuit reading (“A” reading) is less than 100 millivolts, determine cause for low reading, proceed to

Section B below.

B. Thermopile Output Reading Check

(“B” Reading - Thermostat contacts OPEN - Main burner OFF)

1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot

voltage, 325 millivolts minimum. If the minimum milli-volt reading is not obtainable, replace pilot.

CONNECT

METER

SWITCH

OR

METER

CHECK

TO

LEADS TO

THERMOSTAT

READING

TEST

TEST

TERMINALS

CONTACTS

SHOULD

BE

A

COMPLETE

2 & 3

CLOSED

CLOSED

SYSTEM

B

THERMOPILE

1 & 2

OPEN

OPEN

OUTPUT

CHECKING SYSTEM OPERATION

The milli-volt system and individual com-
ponents may be checked with a milli-volt
meter having a 0-1000 mV range. Conduct
each check shown in chart below by con-
nection meter test leads to terminals as
indicated.

CONNECTING REMOTE RECEIVER (Figure 21)

THESE INSTRUCTIONS SUPERCEDE THE SECTION
ENTITLED “HEARTH MOUNT” IN THE MILLI-VOLT
HAND-HELD REMOTE INSTRUCTIONS SUPPLIED
WITH THE REMOTE.

1. Remove cover on control panel to show opening for remote

receiver.

2. Connect the remote connectors located in the unit.
3. Slide remote receiver in the opening of control panel. Use

two screws provided to attach remote receiver to the control
panel.

4. Replace Cover.

NOTE: Do not place remote in combustion chamber.

Figure 21 - Installing Remote Receiver

Remote
Receiver

Cover

Advertising