Ta bl e : C h a r a c t e r i s t i c s o f I nv e r t e r

1- 1

Model

Output

Nominal

Input

Max.

Nominal Output AC Amperes at

Number

Power

Input

Voltage

Input DC

Selectable Output Voltage of:

Rating

Voltage

Range

Current

(VA/Watts)

(Vdc)**

(Vdc)

Amperes

120V

220V

230V

240V

63204*

2000/1680

-48

42 to 57

60

16.6

8.4

8.4

8.4

63104*

1000/840

-48

40 to 60

30

8.3

4.2

4.2

4.2

63054*

500/420

-48

40 to 60

16

4.2

2.1

2.1

2.1

*Model number is followed by a two-digit dash number:

-92 = Inverter with Status indicators.

-94 = Inverter with Status indicators, Digital LCD, and Static Transfer Switch.

**DC voltage rating is given with respect to earth or chassis ground.

0.5 microsecond, 100 kHz ringing wave with 6000V peak,
with no resulting damage per IEEE587.

Less than 30 dBrnC.

80% minimum (on-line mode).

97% typical (off-line mode).

1.5.3

Efficiency

1.5.2

DC Input

Conducted

Emission

1.5.1

Surge Withstand

Capability

1.5

Electrical

Specifications

1.4

Characteristics

of Model

86-153061-00

1 — 3