Ta bl e : Tro u b l e s h o o t i n g C h e ck l i s t

4- 2

SYMPTOM

POSSIBLE CAUSE

RECOMMENDED PROCEDURE

No response when DC circuit

Polarity reversed on DC Input

Check input connections and reverse

breaker is turned ON.

connections. If this is the

if wrong. Remove the inverter module

Inverter STATUS indicator

case, the internal Soft Start

from the receiver cabinet. The soft

remains non-illuminated

fuse will need to be replaced.

start fuse (F1) is located in an opening

on the right hand side of the module. A

spare fuse has been supplied with this

manual. Replace F1 and re-install the

module.

Inverter start up but STATUS

Overload.

Connect the load directly to the AC

indicator goes to RED after lamp

power source and measure the current

test start-up load sequence.

and watts.

Incorrect Inverter output voltage Disconnect load. Turn system ON. Use

or frequency.

the meter function on the front panel or

multimeter to check output voltage and

frequency.

Wrong input voltage.

Check input source and system

specification. If Inverter was powered

up with the 230 VAC on the input and

the Inverter was set for 120, damage to

the Inverter module is possible. Return

the unit to the depot for repair.

Maintenance Bypass relay

Turn off the DC circuit breaker on the

defective.

front panel of the inverter module.

Turn off the AC input circuit breaker and

disconnect the AC input wires. Turn on

the DC circuit breaker on the front panel

of the inverter module. If the inverter

STATUS indicator goes to RED, return

inverter module to depot for repair. If

STATUS indicator goes to GREEN,

inverter is OK. Verify that no AC voltage

(less than 5VAC) exist on the AC input

86-153061-00

4 — 7

Maintenance and Service

Owner’s Manual