SYMPTOM

POSSIBLE CAUSE

RECOMMENDED PROCEDURE

terminals and that the proper AC output

voltage exist on the AC output terminal

block. If 100-120 VAC or 200-240 VAC

exist on the AC input terminal block,

Maintenance Bypass relay is defective,

replace AC EMI filter board.

Inverter will not start.

DC input voltage is too high or

Measure the DC input voltage using

too low.

a multimeter. Check specifications.

Inverter starts and stops.

Load VA is too high.

Measure load current using Utility

Inverter STATUS indicator

AC power.

illuminated RED.

Inverter starts and Inverter

Load VA is too high.

Measure load current using Utility

STATUS indicator is YELLOW.

AC power.

Bypass STATUS indicator is

Utility AC voltage or frequency

Check utility AC voltage with a multi-meter

YELLOW or RED.

Not in specified limits.

Check frequency to ensure it

agrees with the DIP switch setting in

the inverter module.

After taking these steps, make a record of the display lights
and messages, call your local MGE Field Engineer or call
1-800-523-0142 for assistance.

4 — 8

Maintenance and Service

86-153061-00

Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA