Ta bl e : L C D R e a d o u t D e f i n i t i o n s

1- 2

Column 1 Column 2

Column 3

Power Source Mode / Status Definition

LED status

Power Source

Source

Source Mode

Status

SYSTEM SET TO THE ON-LINE

Inverter

(INVERTER) MODE.

LED

LINE 1

INV:

on

normal

System is on the inverter delivers power to the load.

Green

LINE 1

INV:

on

dc low

Input DC voltage is less than 42 volts.

Yellow

LINE 1

INV:

on

dc high

Input DC voltage greater than 57 volts.

Yellow

LINE 1

INV:

on

overload

Load greater than 125% of rated VA or Watts.**

Yellow

120% for 2 kVA

LINE 1

INV:

off

DC LOW

On Bypass. Input DC voltage less than 39.5 volts.

Red

LINE 1

INV:

off

DC HIGH

On Bypass. Input DC voltage greater than 60 volts.

Red

LINE 1

INV:

off

DC FAIL

On Bypass. Input circuit breaker turned OFF.

Red.

LINE 1

INV:

off

overload

On Bypass. Load >125%, see specification.

Red

120% for 2 kVA

LINE 1

INV:

off

software

On Bypass. Shut down, micro-processor problem.

Red

LINE 2

BYP:

ready

normal

Input AC voltage in tolerance, ready to go to bypass.

Blink Green

LINE 2

BYP:

ready

ac low

Input AC voltage less than 85% of nominal.

Blink Yellow

LINE 2

BYP:

ready

AC LOW

Input AC voltage less than 71% of nominal.

Blink Red

LINE 2

BYP:

ready

ac high

Input AC voltage greater than 110% of nominal.

Blink Yellow

LINE 2

BYP:

ready

AC HIGH

Input AC voltage greater than 112% of nominal.

Blink Red

LINE 2

BYP:

ready

AC FAIL

Input AC returned, inverter NOT phase locked.

Blink Red

LINE 2

BYP:

ready

ac warn

Input AC less than 85%, inverter phase locked.

Blink Red

SYSTEM SET TO THE OFF-LINE

Bypass LED

(BYPASS) MODE.

LINE 1

INV:

ready

normal

Inverter in stand-by, ready to operate

Blink Green

LINE 1

INV:

ready

dc low

Input DC less than 42 volts.

Blink Yellow

LINE 1

INV:

ready

dc high

Input DC greater than 57 volts.

Blink Yellow

LINE 1

INV:

off

DC LOW

Input DC less than 39.5 volts.

Blink Red

LINE 1

INV:

off

DC HIGH

Input DC greater than 60 volts.

Blink Red

LINE 2

BYP:

static

normal

External AC input powering load. Voltage in
tolerance.

Green

LINE 2

BYP:

ready

ac low

Input AC voltage less than 85% of nom. On
inverter

Yellow

LINE 2

BYP:

ready

AC LOW

Input AC voltage less than 71% of nom. On inverter.

Red

LINE 2

BYP:

ready

ac high

Input AC voltage greater than 110% nom. On
inverter.

Yellow

LINE 2

BYP:

ready

AC HIGH

Input AC voltage greater than 112% nom.
On inverter.*

Red

LINE 2

BYP:

maint

normal

Input DC breaker Off, input AC in tolerance.

Green

LINE 2

BYP:

maint

ac low

Input DC breaker Off, input AC less than 85% nom.

Yellow

LINE 2

BYP:

maint

AC LOW

Input DC breaker Off, input AC less than 72% nom.

Red

LINE 2

BYP:

maint

ac high

Input DC breaker Off, input AC greater than
110% nom.

Yellow

LINE 2

BYP:

maint

AC HIGH

Input DC breaker Off, input AC greater than
112% nom.

Red

LINE 2

BYP:

maint

ac warn

Input DC breaker Off, system recovering from
AC hi/low

Yellow

NOTE: In the maintenance bypass mode, the load will be powered from the input AC source,
independent of its voltage level.

* If inverter failure or DC input loss occurs, and AC input voltage is greater than 112% of nominal, the system will shut down

to protect users equipment.

** If overload is not removed, unit will transfer to Bypass, Inverter Ready will be displayed (see specification).

1 — 6

Introduction

86-153061-00

Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA