Ta bl e : R e c o m m e n d e d I n p u t / O u t p u t W i r i n g

2- 1

Model

DC Input

AC Output

AC Input

Current

Current

Current

Max.
Current

63054

16 AMPS

5 AMPS

5 AMPS

Min. Wire
Size

(500VA)

12 AWG

14 AWG

14 AWG

Max.
Current

63104

30 AMPS

10 AMPS

10 AMPS

Min. Wire
Size

(1kVA)

10 AWG

14 AWG

14 AWG

Max.
Current

63204

60 AMPS

17 AMPS

17 AMPS

Min. Wire
Size

(2kVA)

8 AWG

12 AWG

12 AWG

NOTE: Maximum circuit breaker rating for AC input shall be
20 Amperes, Maximum DC input current should be limited
to 50 Amperes. Wire gauge for both AC and DC wiring shall
be selected according to the national electrical code.

WARNING

This product is considered permanently connected equipment and
must have a readily accessible disconnect device incorporated in the
fixed wiring.

ATTENTION

Ce produit est considere comme equipement connecte en permanence
et doit avoir un appareil de deconnexion facilement accessible incor-
pore dans le cablage fixe.

WARNUNG!

Dieses Produkt ist ein fest zusammengefuegtes Geraet und muss eine
leicht erreichbare Abschaltungsvorrichtung im Leitungsnetz enthal-
ten.