Keep the Stove a Safe Distance From

Surrounding Materials

Both a stove and its chimney connector radiate heat in
all directions when operating. A safe installation
requires that adequate

clearance be maintained

between the stove and nearby combustible materials to
ensure that such materials do not overheat.

Clearance is the distance between either your stove or
chimney connector, and nearby walls, floors, the
ceiling, and any other fixed combustible surface. Keep
furnishings and other combustible materials away from
the stove as well. In general, a distance of 48" (1220
mm) must be maintained between the stove and
moveable combustible items such as drying clothes,
furniture, newspapers, firewood, etc. Keeping those
clearance areas empty assures that nearby surfaces
and objects will not overheat.

Safe Ways to Reduce Clearances

Your stove has special clearance requirements that
have been established after careful research, and
testing to UL and ULC standards.

Clearance requirements have been established to meet
most installation possibilities, and they involve the
combination of four basic variables:

When the stove

has no listed heat shield mounted

on it.

When the stove

has a listed heat shield mounted on

it.

When the wall

has no listed heat shield mounted on

it.

When the wall

has a listed heat shield mounted on it.

In general, the greatest clearance is required when you
are placing a stove with no heat shield near a wall with
no heat shield. The least clearance is required when
both the stove and the wall have heat shields. Reduc-
ing a stove clearance may require a listed heat shield
on the chimney connector as well.

Clearances may be reduced only by means approved
by the regulatory authority, or in accordance with the
clearances listed in this manual.

Wall Shields

Wall shields should be constructed of 24 gauge or
heavier sheet metal, or another noncombustible mate-
rial such as 1/2" (13 mm) insulation board or common
brick "laid on flat," with the 3

¹⁄₂

" (90 mm) side down.

(Fig. 13)

Shields must be spaced out from the combustible
surface 1" (25 mm) on noncombustible spacers. The
spacers should not be directly behind the stove or
chimney connector.

Air must be able to flow between the wall and the
shield. At least 50% of the bottom 1" (25 mm) of the
shield should be open and the shield must be open at
the top.

When calculating clearance, always measure from the
top plate of the stove, or, from the chimney connector
itself, to the adjacent combustible surface. Do not
measure from the heat shields of the stove or connec-
tor to the combustible surface.

Air Flow

Stud Wall
Framing

Wall Shield

Noncombustible
spacers and
fasteners

Drywall

Air Flow

Shield

Metal
Spacer

Screen

ST248

Fig. 13 Approved wall shield construction.

Reversing the Flue Collar

Your Resolute Acclaim is shipped with the flue collar in
the top exit position. Depending on your requirements,
you may wish to reverse the flue collar and extension
plate to the rear exit position. The only tool necessary
is a 7/16" wrench.

To reverse the flue collar position:

1. Remove the four fasteners that hold the collar and

extension plate. The fasteners are accessible by
reaching through the flue collar of the stove.

2. Remove the flue collar and extension plate.

3. Examine the exposed gasket; contact your Vermont

Castings Authorized Dealer if the gasket needs to be
replaced.

4. Position the extension plate and flue collar in the

appropriate orientation, making sure the gasket
remains in place. The notched edge of the exten-
sion plate should be next to the griddle.