Checking gas pressure, Connecting remote receiver, Warning – Monessen Hearth DSSNVMB User Manual

Page 12

Advertising
background image

12

46D0550

46D0550

13

��

���

����

���

���

���

CHECKING GAS PRESSURE

AND

CONNECTING REMOTE RECEIVER

The heater gas inlet connection is 3/8" NPT at the valve. The
inlet is located on left side of stove. Remove front control plate
to better access the inlet.
When tightening up the joint to the valve, hold the valve securely
with a wrench to prevent movement.
Test all gas joints from the gas meter to the heater valve for

leaks using a gas analyzer or soap and water solution after completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and the control set to HIGH.

Connecting directly to an unregulated
propane/L.P.G. tank can cause an
explosion.

W

ARNING

MILLIVOLT CONTROL (FIGURE 5)
The valve regulator controls the burner pressure which should
be checked at the pressure test point.
If outlet pressure is low, check inlet pressure against data plates
or manual.

Turn captured slotted screw counter clockwise 2 or 3 turns and
then place tubing to pressure gauge over test point (Use test
point “OUT” closest to control knob). After taking pressure
reading, be sure and turn captured screw clockwise firmly to
re-seal. Do not over torque. Check for gas leaks.

NOTE: Remove control panel to access gas valve.
Ignitor battery module is located on back of panel.

Figure 5 - Pressure Test Point Location

Milli-Volt Control

Test Port “OUT”

CONNECTING REMOTE RECEIVER

1. Remove cover on control panel to show opening for

remote receiver. See Figure 6.

2. Cut cable to length (approximately 12") for placement in

the fireplace.

3. If wires are not stripped, strip back

1

/

4

" of the insulation

from free end of each wire. Do not cut off wire connec-
tor.

4. Connect two .25 female connectors to the wires at free

end of the cable.

5. Insert the wire connector into the receiver. If remote does

not have plug-in connector, strip back

1

/

4

" of insulation.

Insert wires into terminal and tighten screws.

6. Connect the connectors to the two .25" male connectors

located on the left side when facing the unit (Figure 6).
Do not let the wires touch the grate or burners.

7. Slide remote receiver in the opening of control panel.

Use two screws provided to attach remote receiver to the
control panel. See Figure 6.

8. Replace cover with cover supplied with remote. See

Figure 6.

Figure 6 - Installing Remote Receiver

Remote
Receiver

Cover

NOTE: Do not place remote in combustion chamber.