Troubleshooting, Warning – Monessen Hearth DSSNVMB User Manual

Page 25

Advertising
background image

24

46D0550

46D0550

25

OBSERVED PROBLEM

ODS/pilot lights, but flame
goes out when control knob is
released.

Burner does not light after ODS/
pilot is lit.

Burner backfires during com-
bustion.

Slight smoke or odor during
initial operation.

Logs appear to smoke after ini-
tial operation.

Heater produces a whistling
noise when burner is lit.

No gas to pilot.

POSSIBLE CAUSE

1. Control knob not fully pressed in.
2. Control knob not pressed in long enough.

3. Appliance shutoff valve not fully open.
4. Thermocouple connection loose at

control valve.

5. Pilot flame not touching thermocouple, which

allows thermocouple to cool, causing pilot
flame to go out.

6. Thermocouple damaged.
7. Control valve damaged.

1. Inlet gas pressure is too low.
2. Burner orifice diameter is too small.
3. Burner orifice is clogged.

1. Manifold pressure is too low.
2. Burner orifice is clogged.

1. Burner orifice is clogged or damaged.
2. Burner is damaged.
3. Gas regulator defective.

1. Vapors from paint or curing process of logs.

1. Turning control knob to HIGH position when

burner is cold.

2. Air in gas line.

3. Dirty or partially clogged burner orifices.

1. LP-regulator shut down due to inlet pressure

too high.

REMEDY

1. Press in control knob fully.
2. After ODS/pilot lights, keep control

knob pressed in for 30 seconds.

3. Fully open manual shutoff valve.
4. Hand tighten thermocouple connection

until snug, then tighten 1/4 turn more.

5. Contact local gas company. This prob-

lem could be caused by either low gas
pressure, or a dirty or partially clogged
ODS/pilot.

6. Replace pilot.
7. Replace control valve.

1. Contact qualified service person.
2. Replace burner orifice.
3. Clean orifice.

1. Contact local gas company.
2. Clean burner or replace burner orifice.

1. Clean burner or replace burner orifice.
2. Replace burner.
3. Replace gas regulator.

1. Problem will stop after a few hours of

operation. Open a window for the first
few hours.

2. Log heater is intended to be smokeless.

Turn OFF heater and call qualified ser-
vice person.

1. Turn control knob to LOW position and

let warm up for a minute.

2. Operate burner until air is removed from

line. Have gas line checked by local gas
company.

3. Clean burner or replace burner orifice.

1. Verify LP tank regulator is installed and

set at 11" to 13" w.c.

TROUBLESHOOTING

If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and
the heater may backfire when lit. If the gas quality or pressure is low, contact your local
gas supplier immediately.