MITSUBISHI ELECTRIC T-60 User Manual

Page 102

Advertising
background image

Available Commands:

The commands listed in the table below list the commands available for the
Mitsubishi FX series interfaces.

CALL PLCINIT Statement

Purpose:

This command is used to initialize communication with the FX. CALL
PLCINIT must be issued prior to any other communication (reading or
writing) to the specified PLC. CALL PLCINIT initializes the BAUD rate to

9600 Baud, 7 data bits, even parity. Either COM 1, COM 2, RS422, and
RS232 can be specified. Note that on T-60 ’s COM1, RS422 is

recommended. If the CALL PLCINIT command fails, the T-60 Series unit
will break your program and generate the error message “PLC link not
established.” If this make sure that the connections and communications

configurations are correct. If they are OK, check to make sure that the FX is
powered up and ready to accept Commands.

Cmd #

Command

PLC Data Type

Address

Size

1

2

Inputs

X

0-177

BIT

3

Outputs

Y

0-177

BIT

4

Registers

D

0-511

8000-8255

Word

5

6

7

8

9

Auxiliary Relays

M

0-1023

8000-8255

BIT

10

Timer Contacts

T

0-255

BIT

11

Counter

Contacts

C

0-255

BIT

12

Timer Value

T

0-255

WORD

13

14

Counter Value

C

0-199

WORD

15

Table 15

Mitsubishi FX Series Interface

Commands

T-60 Operator's Manual

94