Figure 13. Connecting Loads

Connecting Loads

Loads can be connected to the generator by the UVWO terminal
lugs or the convenience receptacles. (See Figure 13). Make
sure to read the operation manual before attempting to connect
a load to the generator.

To protect the UVWO output terminals from overload, a 3-
pole, 1,600 amp,

main circuit breaker is provided. Make

sure to switch

ALL circuit breakers to the "OFF" position

prior to starting the engine.

DCA-600SSK — OUTPUT TERMINAL PANEL OVERVIEW

Over Current Relay
An

over current relay (Figure 14) is connected to the main

circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the

reset button on the over cur-

rent relay must be pressed. The over current relay is lo-
cated in the control box.

Figure 14. Over Current Relay

Maximum Power Output (KW)

The entire load connected to the UVWO output terminal lugs,
duplex and auxiliary receptacles must not exceed 528 kW in
standby or 480 kW in prime output.