PAGE 46 — DCA-600SSK — OPERATION AND PARTS MANUAL (STD) — REV. #7 (04/30/10)

Figure 52. Voltage Adjust Control Knob

Figure 53. Ammeter (No Load)

13. The ammeter (Figure 53) will indicate zero amps with no

load applied. When a load is applied, the ammeter will
indicate the amount of current that the load is drawing
from the generator.

12. The generator's AC-voltmeter (Figure 51) will display the

generator’s output in VOLTS. If the voltage is not within
the specified tolerance, use the voltage adjustment
control knob (Figure 52) to increase or decrease the
desired voltage.

Figure 51. AC Voltmeter

Figure 47. Pre-Heat Lamp

8. Place the

engine throttle lever in the “LOW” position

(Figure 48).

Figure 50. Frequency Meter (Hz)

Figure 49. Engine Ignition Switch

9. Turn the ignition key to the “START” position (Figure 49)

and listen for the engine to begin cranking. After the
engine starts release the ignition key.

Figure 48. Engine Throttle Control

10. Once the engine has started, let it run for 3-5 minutes,

then turn the throttle handle control (Figure 48) to the
HIGH” position.

6. When starting the generator in COLD weather conditions,

turn the

ignition key to the “PREHEAT ” position (Figure 46),

Figure 46. Ignition Switch (Pre-Heat)

11. The generator's frequency meter (Figure 50) should be

displaying the 60 cycle output frequency in HERTZ.

7. Verify that the pre-heat lamp(Figure 47) is lit (ON) before

starting engine.

5. Set the

battery ON/OFF switch (Figure 45) to the “ON

position.

Figure 45. Battery ON/OFF Switch

DCA-600SSK— GENERATOR START-UP PROCEDURE (MANUAL)

Pre-Heat

Lamp