2-13

SECTION 2

INSTALLATION

Figure 2-27

Utility Connection Locations

VII.GAS SUPPLY

A. CONNECTION
Check the oven’s gas supply requirements before making

the gas utility connection. Gas supply requirements are

listed on the oven’s data plate (Figure 2-26) and in the Oven

Specifications table (Page 1-1 of this manual).
Check the oven data plate (see Figure 2-26) to determine

the type of gas (Propane or Natural) to be used with the

oven.
Refer to the instructions in the gas hose package (included

in the Base Pad Kit) before connecting the gas line. One

gas line connection method is shown in Figure 2-28;

however, compliance with the applicable standards and

regulations is mandatory.
Inlet, regulated, and pilot gas pressure readings can be

taken using a “U” tube manometer at the tap locations

shown in Figure 2-29.
One 90° elbow equals a 4’ (1.22m) length of pipe. The

recommended pipe sizes are larger than usually required

to eliminate any operation problems. It is much less

expensive to make the initial installment large enough to do

the job rather than redoing the job later.

NOTE

The installation must conform with local codes or in the

absence of local codes, with the National Fuel Gas

Code, ANSI Z223.1-latest edition.

In Australia, the installation must conform with AGA

Code AG601 and with any requirements of the

appropriate statutory authority.

CANADIAN:

CAN/CGA-B 149.1 Natural Gas Installation Code

CAN/CGA-B 149.2 Propane Installation Code

CAUTION

DURING PRESSURE TESTING NOTE ONE OF

THE FOLLOWING:

1. The oven and its individual shutoff valve must

be disconnected from the gas supply piping

system during any pressure testing of that system

at test pressure in excess of 1/2 psi (3.45 kPa).
2. The oven must be isolated from the gas supply

piping system by closing its individual manual

shutoff valve during any pressure testing of the

gas supply piping system at test pressure equal to

or less than 1/2 psi (3.45 kPa).
3. If incoming pressure is over14” W.C. (35mbar),

a separate regulator MUST be installed in the line

BEFORE the individual shutoff valve for the oven.

WARNING: To prevent damage to the

control valve regulator during initial turn-

on of gas, it is very important to open the

manual shutoff valve very slowly.

After the initial gas turn-on, the manual shutoff

valve must remain open except during pressure

testing as outlined in the above steps or when

necessary during service maintenance.

Lower Oven

Upper Oven

Electrical

Junction Box

Gas Utility

Connection

Gas Utility

Connection

Electrical

Junction Box