INSTALLATION

GENERAL REQUIREMENTS

CAUTION:

EQUIPMENT MUST BE INSTALLED BY A QUALIFIED

HEATING PERSON.

CAUTION:

ONLY “CLASS A” ALL-FUEL OR SOLID FUEL CHIM-

NEYS INTENDED FOR USE WITH YOUR WOOD-

CHUCK SHOULD BE USED.

FIRST AND ABOVE ALL is safety for you and your

family.

MUST USE: Class A Masonry or ULC listed, manufac-

tured Class A All Fuels Chimney.

RECOMMENDED SIZE: Rectangular 8"x12" or Round

8".

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE

SERVING ANOTHER APPLIANCE. The Woodchuck is

to be used in conjunction with a listed gas or oil fired

furnace or as a central furnace.

ELECTRICAL SUPPLY: 115 volts, 60HZ, 1 Phase,

less than 12 amps.

Install system with 0.2 static pressure.

Flue setting .06 W.C. Max to .04 W.C. Min.

Wood or coal related fires are caused almost exclu-

sively by installation, operation or maintenance errors;

but not by unsafe equipment.

IMPORTANT: Check with your local state and federal

codes on installation at your local fire department.

PLACEMENT AND MINIMUM CLEAR-

ANCES

CAUTION:

FURNACE MUST BE INSTALLED ON A NON-COM-

BUSTIBLE FLOOR OR 3/8" THICK FIREPROOF MILL-

BOARD OR EQUIVALENT.

Locating your unit is very important for proper draft and

most efficient heating possible. See figure 7.

FIGURE 7 LOCATING THE WOODCHUCK