Air duct installation – Meyer WOODCHUCK 526 User Manual

Page 19

Advertising
background image

19

FIGURE 10 A BAROMETRIC DRAFT REGULA-

TOR AND ITS INTENDED EFFECT

With no draft in chimney, regulator

is closed, no air gets in.

Moderate suction in chimney pulls regulator open

enough to maintain desired draft for appliance.

Excessive suction in chimney pulls regulator further

open, allowing substantial air into chimney connector.

MANUAL DAMPER MAY BE

INSTALLED BETWEEN BAROMETRIC

DAMPER AND CHIMNEY

AIR DUCT INSTALLATION

SPECIAL AIR FLOW

CONSIDERATIONS FOR

WOOD/COAL FURNACES

With Wood/Coal furnaces, a special concern is pre-

venting wood joists and flooring close to the hot air

ducts and plenum from overheating. A fire hazard is

created by the hot air flow circulating through ducts not

designed for such high temperatures. Most Wood/Coal

furnaces produce much hotter air than oil or gas fired

units. So most clearances from the existing ducts and

plenum are usually inadequate with a supplemental

Wood/Coal furnace installation.

When installing the air duct, follow recommended

clearances shown in figure 11.

The plenum on the Woodchuck should be 20"x23" and

no less than 18" high while maintaining a minimum of

18" clearance to the ceiling or other combustible mate-

rial. In a power outage situation, excessive heat

buildup at the plenum top may be dangerous, so make

sure clearances are maintained. For the Model 4000

allow at least 4" from ceiling to plenum.

The ducts, fittings, grilles and registers should be

sized so that the total external static pressure does not

exceed .02 W.C. inches while developing air velocities

of 600 ft/min to 1000 ft/min at the registers. NEVER

supply less than 150 sq. in. of heated air outlet area.

Cold air returns must be at least equal in size to the

heated air outlets and preferably 10% larger. Every

Woodchuck furnace MUST be installed with a cold air re-

turn.

ADD-ON INSTALLATIONS

Before installing your Woodchuck furnace, consult

your furnace man and local state building codes to de-

termine if your furnace will accept an add-on applica-

tion. Some small furnaces and especially counter-flow

furnaces may not be used in add-on installations.

Once it has been determined that your existing fur-

nace will accept an add-on installation, we recommend

a parallel installation, with direct (ducted) feed of re-

turn air to the Wood/Coal furnace, see figure 12. The

back flow prevent damper assures that when either

unit is operating by itself, the hot air will flow into the

home, and not flow back through the other furnace.

Figure 13 shows a central installation.

We do not recommend supplemental wood furnace

installations with series connection. These types of

installation are not advisable in spite of their simplicity,

see figure 14.

Advertising
This manual is related to the following products: