2. Installation

Remote Power Off communication port (16)

(see page 8)

Installation of communication cards (optional, standard with the NetPack version)

Installation of a Remote Power Off function must be carried out in compliance with applicable regulations.
In order to fully de-energize devices and Pulsar MX RT with the RPO port, it is necessary:

to use a two-position switch (Normally Open or Closed contact should be held more than 1 second to be taken into account).

to connect to this RPO switch a device that allows to trip all breaker(s) located upstream

(1)

and downstream

(2)

Pulsar MX

RT. This can be achieved by means of a shunt trip.

(1) : If not, the output devices could be powered again through static switch when the two-position switch is released.
(2) : If not, the output devices will remain powered several seconds after the RPO activation.

Please, notice that the internal batteries will remain connected to the power sub-module after RPO activation.

The cable is not included.

Remote power off contact normally open

Remote power off contact normally closed

Signal:

- activation voltage: 5 V DC to 27 V DC.
- current: 10 mA max.

Communication card (restricted access)

It is not necessary to shutdown the UPS
before installing a communications card.

1 - Remove the slot cover secured by two
screws.
2 - Insert the communications card in the slot.
3 - Secure the card with both screws.

RJ12 (6p6c)

5 4 3 2 1

6

5 V DC to 27 V DC

5 4 3 2 1

6

RJ12 (6p6c)

5 V DC to 27 V DC

RS232

CONTACTS BAT NO. RPO

PARALLEL

SWITCHED

GROUP 2

SWITCHED

GROUP 1

Card Settings

RS232 Download

66074

UPS

data

Reset

100 10

1 2

ON

ETHERNET

RS232

IP=

MAC=00E0D8FF855E

Advertising
This manual is related to the following products: