4. Access to measurements and personalisation data

Battery settings

4.5 Maintenance

4.6 Personalisation using external software

Function

Factory setting

Options

Comments

Auto Battery Test

Everyweek

No test / everyday /
everyweek /everymonth

Low Batt Warning

20%

0 to 100%

1% increment

User Batt Settings

UPS reads number of
battery modules
connected

From 0 to 40 Ah

5 Ah increment

Deep Disch Protect

Yes

No

Protection against deep discharge.
If disable, MGE UPS SYSTEMS
warranty will be void

Function

Sub-Function

Option / Display

Comments

Model

Power Module

SN: xxxxxxxxx
SOFT: xxx
NT: xxx

Serial number
Soft version
Technical level

Frame

Alarm History

Read

Description
Date Hour
Alarm xxx

10 alarms can be stored
automatically

Erase

No / Yes

Manual Batt Test

Manual Battery Test

No / Yes

Led & Buzzer Test

Led & Buzzer Test

No / Yes

Life Cycle Monitoring

LCM

Enable / Disable

Life cycling monitoring alarms

Statistics

Auto Statistics

Statistics

You need to register at
www.mgeups.com/Icm to get the
code and get access to free statistics

Custom Statistics

Reset Date ?
Are you sure ?

Operation Limits

Operation Limits

Automatic alarms displayed when
UPS is operating near the limits

Insert the Solution-Pac CD-ROM in the drive.

On the first navigation screen, select

"

Point to Point solution

"

and follow the instructions on how to install the Personal

Solution-Pac software.

Then select

"

Settings

"

,

"

Advanced settings

"

and

"

UPS settings

"

.

Note that only the Windows versions of the Personal Solution-Pac software offer this possibility.