2. Installation

2.7 Connection of input/output power cables on UPS terminals

This type of connection must be carried out by qualified electrical personnel.

Before carrying out any connection, check that the battery circuit breaker (19) (see page 8) and that the upstream protection

device (Normal AC source) is open ("0").

Use included insulated ferrules with stranded wires.

1 - Remove the terminal block cover (2
screws) with the included screwdriver.
2 - Insert the Normal AC cable through the
cable gland (8).
3 - Connect the 3 wires to the Normal AC
terminal block.

Always connect first the
earthing wire.

4 - Insert the output cable through the cable
gland (7).
5 - Connect the 3 wires to the output terminal
block.
6 - Refit the terminal block cover and tighten
the cable glands.
7 - Secure the terminal block cover by means
of 2 screws.

7

8

1

7

8

2

4

5

3

7

6