86-108814-00 B01

Installation and Operation

2 — 5

Installation and User Manual

Figure 2-4: Power-Sure™ 700 — 225-300kVA Mechanical Cabinet Measurements.

2.4

General Operation Notes

The Power-Sure™ 700 Power Conditioners provides the triple function of isolation, noise attenuation and voltage

regulation. The first two functions are provided by the power transformer, where as the third function of voltage regula-

tion is achieved through solid state thyristors (SCRs) connected to taps on the power transformer. A micro-processor

monitors and controls the overall function of regulating the system.

The power transformer is manufactured with a unique method of shielding which produces very low capacitive

coupling between the primary and secondary. This low coupling provides excellent attenuation of the common-mode

noise. In addition, special care is taken in the design of the transformer to attenuate transverse-mode noise above

1000 Hz. The power transformer has taps to which solid state switches (SCRs) are connected.

The voltage regulator incorporated in the Power-Sure™ 700 Power Conditioners is microprocessor controlled to

achieve optimum correction time of input voltage sags and surges. The response time is typically one (1/2) cycle for

100% correction, therefore, a very smooth switch takes place undetected by computer equipment.

41.5"

(1054.1m)

77.207"

(159.9m)

35"

(889m)

2.75"

(69.85m)

56"

(1422.4m)

50.5"

(1282.7m)

2.75"

(69.85m)

32"

(1812.8m)

POWER ON

ALERT

INPUT
CIRCUIT
BREAKER
(TERMINATE
INPUT
CABLES
AT CIRCUIT
BREAKER)

OPTIONAL
BYPASS
SWITCH
(OPEN
DOOR
FOR
ACCESS)

CLEARANCE
HOLE
FOR 1/2"
MOUNTING
BOLT

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

REAR VIEW

G N L3 L2 L1

5.5" (139.7m)

3.25" (82.55m)

4.625"
(117.47m)

OUTPUT TERMINAL DETAIL .25 X 4 COPPER BUSS

5.25" (133.35m)

4.625"

(117.47m)

1.75" (44.45m)

1.73" (43.94m)

1" (25.4m)

1" (25.4m)

2" (50.8m)

32"

(1812.8m)

OUTPUT
TERMINALS
CUSTOMER
SIDE

TOP VIEW

LIFT-OFF

ACCESS PANEL

9" (228.6m)

45"
(1143m) Clearance

CABINET COOLING FAN

LIFT-OFF
ACCESS PANEL

OUTPUT CONDUIT LOCATION

INPUT CONDUIT LOCATION

8" (203.2m)

8" (203.2m)

5" CLEARANCE REQUIRED
(THIS SIDE)

OUTPUT ACCESS PLATE

OUTPUT TERMINALS

LIFT-OFF ACCESS PANEL

6" CLEARANCE REQUIRED

(THIS SIDE)

36" CLEARANCE REQUIRED