Installation and Operation

Table 2-1: 480 VAC Input and 208 VAC Output Wire Size Chart.

Unit Size

Input

Input

Minimum

Maximum

in kVA

Breaker

Wire

Ground Wire

Output

Size

Size

Size

Current

10

15 Amp

#10

#10

28

15

25 Amp

#10

#8

42

25

50 Amp

#8

#4

70

30

50 Amp

#8

#4

83

45

80 Amp

#6

#2

125

50

80 Amp

#6

#2

139

75

125 Amp

#1

#6

208

100

150 Amp

1/0

4/0

278

125

200 Amp

1/0

2 pcs 1/0

347

150

225 Amp

1/0

2 pcs 2/0

417

225

350 Amp

4/0

2 pcs 250

625

300

500 Amp

2 pcs 2/0

3 pcs 250

833

Table based on 480 VAC input and 208 VAC output.

Table 2-2: 208 VAC Input and 208 VAC Output Wire Size Chart.

Unit Size

Input

Input

Minimum

Maximum

in kVA

Breaker

Wire

Ground Wire

Output

Size

Size

Size

Current

10

40 Amp

#8

#10

28

15

60 Amp

#8

#8

42

25

110 Amp

#4

#4

70

30

110 Amp

#4

#4

83

45

175 Amp

#1

#2

125

50

175 Amp

#1

#2

139

75

300 Amp

2/0

2/0

208

100

350 Amp

4/0

4/0

278

125

450 Amp

2 pcs 1/0

2 pcs 1/0

347

150

600 Amp

2 pcs 3/0

2 pcs 3/0

417

225

800 Amp

2 pcs 250

2 pcs 250

625

300

1200 Amp

3 pcs 250

3 pcs 250

833

Table based on 208 VAC input and 208 VAC output.

NOTE:

Refer to NEC for output wire size based on output breaker size and Article 310

Section 8A.

2 — 7

Installation and User Manual

86-108814-00 B01