3 —9

Installation and User Manual

5.

Turn the input circuit breaker off.

6.

Connect customers equipment.

7.

Energize system.

8.

Repeat Step #4 and adjust as needed.

9.

Be sure over/under detect is connected and if input breaker trips or there is no output voltage, re-calibrate the

detect board or replace board if defective.

3.7

Unit Component Location Diagrams

Figure 3-3: Power-Sure™ 700 — 10-15kVA Major Components.

Figure 3-4: Power-Sure™ 700 — 25-30kVA Major Components (Rear View).

SENSE CARD

CONTROL CARD

INPUT CIRCUIT BREAKER

MULTI-SHIELDED

ISOLATION TRANSFORMER

OUTPUT FILTERING

OUTPUT TERMINAL PADS

INPUT TERMINAL BLOCK

SNUBBER CARD

HEATSINK

SCR POWER MODULE

SEMI-CONDUCTOR FUSES

SENSE CARD

CONTROL CARD

SEMI-CONDUCTOR FUSES

SCR POWER MODULE

HEATSINK

SNUBBER CARD

INPUT CIRCUIT BREAKER

OUTPUT FILTERING

OUTPUT TERMINAL PADS

INPUT TERMINAL BLOCK

MULTI-SHIELDED

ISOLATION TRANSFORMER