CAUTION:

THE CONTROL BOARD (#49120/407415) IS ELECTRICALLY REFERENCED TO

HIGH VOLTAGE, NOT EARTH OR CHASSIS GROUND. EXTREME CARE MUST BE

USED WHEN TAKING MEASUREMENTS ON THE CONTROL BOARD. ANY AC

POWERED INSTRUMENTS MUST BE GROUND ISOLATED PRIOR TO TAKING

MEASUREMENTS. A GROUND ISOLATED INSTRUMENT CASE WILL BE AT THE

HIGH VOLTAGE LINE POTENTIAL.

3.9.2 Control Card Adjustment Procedure

1.

Prior to attempting any adjustment, measure the incoming voltage to the unit. Assure the voltage level is within

the specified input range of the unit.

2.

Turn off power to unit.

3.

Remove all loads from the output of unit under adjustment.

4.

Remove both TB2 connectors on all control boards #49120/407415. Turn power on.

5.

With DC voltmeter on the millivolt scale check between TP1 and TP GND and adjust P2 so meter reads “0”

millivolts or as close as possible.

Figure 3-11: Power-Sure™ 700 Controller Card (Top View).

6.

Use Formula X below to calculate the next adjustments. You must calculate each input phase for each control

card or a total of 3 calculations:

For phase 1 control card, measure AC input at Line 1 to Line 2.

For phase 2 control card, measure AC input at Line 2 to Line 3.

For phase 3 control card, measure AC input at Line 1 to Line 3.

115V 208V 240V

TP

GND

TP1

TP2

GRND

P2

TB2

TB2

TB2

TB3

P1

49120 /

407415

1

17

1

Maintenance

Power-Sure™ 700 —

Three Phase Power Conditioners

3 —16

86-108814-00 B01