1.

Prior to use, charge the Ellipse Premium
battery for 8 hours by connecting to utility
power. This conditions the battery for long life.

2.

After an outage, a few hours are required
to reach a full recharge.

Notes:
1.

Ellipse Premium is equipped with a lead-
acid battery(s), which must be disposed
of in accordance with local regulations.
MGE will accept UPS and/or batteries for
recycling free of charge. Contact us at
the phone number shown in the recycling
section of this manual.

2.

Battery life is cut in half for every 15
degrees above 75°F. Plug in and
recharge the UPS at least every six
months if the UPS is taken out of service.

Battery Replacement for
500/650/800/1200 Models

CAUTION: Read and follow safety
instructions before removing batteries.
This must be done by qualified
personnel due to risk of high energy.

• Switch off the UPS (on/off switch) and dis-

connect it from utility power and critical loads.

Remove watches, rings or other metal
objects.

Use tools with insulated handles.

1.

In accordance with local regulations and
proper disposal of Ellipse Premium
battery(s), it is necessary to remove
them from UPS chassis. This requires
opening the trap door located on the
side of the UPS.

2.

Observe and note battery connections
prior to removal. Follow operations
pictured, take off the foot (A), open the
door (B), remove and unplug the battery
for recycling (C). Install new battery,
reattach wires observing polarity (red to
"+" terminal, black to "-" terminal). For
Models 650/800/1200, be sure to
reconnect the jumper cable between the
"+" of battery one to the "-" of the second
battery. Repeat the procedure for the
second and third batteries (see diagram

MGE UPS Systems

3400724000

page 4

Battery Replacement

!

B

!

C

Red

Blk.

1

Model 500/650/800/1200

E N G L I S H

MGE UPS Systems

Ellipse Premium User’s Manual

page 7

!

!

Resolução de Problemas

Identificação do Modelo

Modelo do

Comunicações

Proteção de Fax,

Núm. da

Código UPC

Ellipse

Modem/Rede

Peça da MGE

Premium

500 VA

USB

89320

635760893205

500 VA

RS232

89321

635760893212

650 VA

USB

89323

635760893236

650 VA

RS232

89324

635760893243

800 VA

USB

89326

635760893267

800 VA

RS232

89327

635760893274

1200 VA

USB

89329

635760893298

LED " " (verde) desligado,
No-Breaks sem saída

No-Break oferece pouco
ou nenhum tempo
de reserva

LED " " pisca (verde)
alarme audível emite
freqüentemente um bipe (No-Break
transfere à bateria)

LED " " (vermelho), alarme
audível emite bipes

LED " " (verde), alarme audível
emite 1 bipe a cada 10 segundos

LED " " (verde), alarme audível
emite 1 bipe a cada 3 segundos

LED " " (vermelho),
alarme audível emite bipes

LED " " (vermelho) e
LED " " (verde)

Certifique-se de que o No-Break esteja ligado na tomada, a
força CA está "ligada" no No-Break e que o próprio No-
Break esteja "ligado"

Carregue o No-Break da noite para o dia e tente
novamente. Após 3 a 5 anos, considere trocar as baterias se
o tempo de reserva for muito curto (MGE P/N 3088201000).

Excesso de eventos de baixa voltagem ou voltagem com
defeitos na tomada.
Tente outra tomada.

Falha interna em potencial. Reinicie o No-Break. Procure
assistência se o LED reaparecer.

No-Break operando com bateria devido à queda de
força na rede.

No-Break operando com bateria e bateria prestes
a esgotar-se.

No-Break levemente ou muito sobrecarregado. Reengatilhe
o disjuntor no No-Break, caso necessário. Reduza a carga e
reinicie o No-Break.

Falha na bateria. Recarrregue a bateria. Substitua a bateria
se a falha reaparecer.

A MGE oferece uma linha de telefone grátis para o suporte técnico dos clientes nos EUA e
Canadá. Ligue para obter ajuda conforme indicado na seção "Serviço e Peças" deste manual ou
faça uma visita ao nosso web site em: www.mgeups.com

Condição

Item(ns) a Verificar

P O R T U G U Ê S

A

A

Model 500/650/800/1200

Model 500

above). It is normal for a small spark to
occur upon connection. Close door and
reinstall foot. Reconnect input cord and
critical loads. Restart UPS.

US

MGE GREEN SWEEP

Call MGE to return your UPS for free
recycling to a US EPA-certified recycling
center and help protect our environment.