Moxa Technologies 6110 User Manual

Page 34

Advertising
background image

4-8

Modbus Settings

Setting Value Notes

Modbus RTU Slave

1

Modbus ASCII Slave

2

Modbus RTU Master

3

Attached Serial Device type

Modbus ASCII Master

4

Set the Modbus type of the

serial device attached to

NPort 6110’s serial port.

Initial delay time

100 to 3276 ms;

default = 100 ms

NPort Modbus Gateway

provides this setting for

those PLCs that need a

longer time for their

system to be initialized.

Modbus/TCP Slave device setting

Remote Modbus Slave IP

IP address assigned to

the remote Modbus

slave device.

Valid when the attached
serial device is a Modbus
RTU/ASCII Master.

TCP Port No.

default = 502

Set this value to 0 (zero) to
disable the corresponding
Modbus/TCP slave device.

ID No. Range

1 to 247

The unique Modbus ID

number assigned to the

Modbus device.

5


Additional Information

1. When the serial Modbus device is running in Modbus/RTU Slave mode, the

NPort Modbus Gateway is ready to connect automatically to Modbus/TCP

Master devices. Up to 7 Modbus/TCP master devices can connect to one

serial Modbus slave device.

2. Modbus ASCII Slave mode works the same as Modbus/RTU slave mode,

except that the data format is Modbus/ASCII.

3. When the serial Modbus device is running in Modbus/RTU Master mode, the

NPort Modbus Gateway is ready to connect automatically to Modbus/TCP
slave devices. You will also need to configure the IP address for up to 4
Modbus/TCP slave devices that can be connected to over the Ethernet
network.