Moxa Technologies 6110 User Manual

Page 36

Advertising
background image

4-10

Advanced Modbus Settings

Setting Value Notes

Enable (Default)

Auto Slave Unit ID

Disable

Select Enable when

multiple Modbus devices

are accessible at the same

IP address.

1

Character Timeout

10 to 3000 ms

(default = 100 ms)

This parameter is active

when the attached serial

device is set to

Modbus/RTU.

2

Message Timeout

10 to 3000 ms

(default = 1000 ms)

Allows you to configure

the message timeout for

communication between

connected Ethernet or

serial Modbus devices.

Modbus/TCP Exception

default = 502

This parameter is active

when the Modbus

Gateway connects a

Modbus/TCP Master with

Modbus serial slave

devices.

3


Additional Information

1. Modbus/TCP protocol contains a “Unit ID” field to identify multiple Modbus

slave devices accessible at a single IP address. When the Modbus/TCP

command contains a Unit ID, the Modbus Gateway can pass the Unit ID to

Modbus serial devices. This allows you to link to multiple serial devices with

a Modbus Gateway. Some PLCs assume that each IP connects to only one

device. In these cases, the Unit ID can be set “0,” but you must manually

assign a Unit ID (between 1 and 247) to the connected serial device.

However, each Modbus Gateway can connect to only one serial device.

This setting is valid when [Attached Serial Device type] is set to [Modbus

RTU Slave ] or [Modbus ASCII Slave].

Enable: Uses the Unit ID in the Modbus/TCP packet. This is the default

setting.

Disable: Uses the predefined Unit ID instead of Modbus/TCP’s.

ID: The

predefined Unit ID value, ranging from 1 to 247, which is valid