ST4125G/ST6125G SUBMERSIBLE PUMP• OPERATION MANUAL — REV. #0 (11/18/10) — PAGE 13

Float Switches

For unattended operation of the submersible pump two
single fl oat switches (Model SW-1WOPA) will be required.
These fl oat switches can be connected directly to a control
box (bare wires) and will allow the pump to turn on and off
depending on the length of the tether.

FLOAT SWITCHES

Figure 6. Float Switch Application

Mounting The Float Switches

1. Determine the required cord tether length as shown

in Figure 3 and Table 2.

2. Place the cord into the clamp as shown in Figure 6.

3. Secure the clamp to the discharge hose as shown in

Figure 6. DO NOT install cord under hose clamp.

4. Using a screwdriver, tighten the hose clamp. DO NOT

over- tighten. Make sure the fl oat cord is not allowed
to touch the excess hose clamp band during operation.

PUMPING

RANGE

MODEL SW-1WOPA

FLOAT SWITCH (2)

3.5 in. (9 cm.)

MINIMUM

TETHER

LENGTH

PUMP

ON

PUMP

OFF

DISCHARGE

HOSE

INPUT POWER

TO CONTROL BOX

FLOAT SWITCH

CABLES (2)

SUBMERSIBLE

PUMP

CONTROL

BOX

CAUTION!

HIGH

VOLTAGE!

CB12/14

RESET

PUMP POWER

CABLE

EXTERNAL 3-PHASE

(230 OR 460 VOLT)

POWER SOURCE

CIRCUIT

BREAKER

RED

WHITE

BLACK

L1

L2

L3

GREEN

GND.