PAGE 14 — ST4125G/ST6125G SUBMERSIBLE PUMP • OPERATION MANUAL — REV. #0 (11/18/10)

FLOAT SWITCHES

CB12/CB14 Control Boxes

For remote pumping applications, both submersible pumps,
require a control box (Figure 7).

The CB12 control box requires 230VAC, 3-phase input
voltage for normal operation, while the CB14 control box
requires 460VAC, 3-phase input voltage. Reference Table 3
for the desired heater. The heater size is determined by the
the full load amps the pump will draw.

These water-resistant control boxes provide electronic
overload protection a watertight enclosure and glands to
prevent water from leaking into the box, and a fl oat switch
interface.

Each control box will require the use of two SW-1WOPA
fl oat switches, no plug, bare wires for direct connection
to the control box. Reference Figure 21 for a schematic
reprensentation of the control box.

NOTICE

Contact Multiquip sales department to order control
boxes as listed in Table 3.

Table 3. Control Box Specifi cations

Control Box

Model No.

Used With

Pump Model

VoltageType

Heater

Size

Full Load

Amps

UL/CSA

Listed

Thermal

Overload

Protection

Float

Switch

Capability

CB12

ST-4125G

230 VAC

Three-Phase

K67

27

YES

YES

YES

CB12

ST-6125G

230 VAC

Three-Phase

K73

39

YES

YES

YES

CB14

ST-4125G

460 VAC

Three-Phase

K56

14

YES

YES

YES

CB14

ST-6125G

460 VAC

Three-Phase

K62

19.7

YES

YES

YES

Figure 7. Electrical Control Box

(Model CB12/14)

CAUTION!

HIGH

VOLTAGE!

CAUTION!

HIGH

VOLTAGE!

CB12/14

RESET

MAN

OFF

AUTO