Goulds pumps, Phv - packaged hydrovar series – ITT BPHV User Manual

Page 14

Advertising
background image

14

Goulds Pumps

PHV - Packaged Hydrovar Series

SELECTING A SET

The first thing to do when selecting a package is to determine the quantity of water required and the pressure it must
supply.

CALCULATING THE FLOW RATE

The quantity of water called

water requirement depends on the type of users, e.g. homes, offices, schools, as well

as their number. The theoretic requirement is the total amount of water required by all the users. In actual fact, since it
is very unlikely that there should be a simultaneous demand by all the users, the

real requirement is lower than the

theoretic one.

CALCULATING THE HEAD

The pressure required depends on the type of user. A number of factors must be taken into account, including the

height of the building, the suction conditions and the flow resistance in the pipes.

SELECTING A BOOSTER SET

According to the required flow rate and head values, it is possible to identify the most suitable type of electric pump.

On two-pump sets the pumps normally act as

back-up for one another. A single pump is normally sufficient to

provide for average requirements, while in conditions of high demand the back up pump may be called in to assist.
With the

cyclic changeover function duty assignment is rotated to ensure both pumps remain active and with

even running hours, so wear is uniform and the use factor is reduced for longer pump life. This system also ensures

continuity of operation in case one of the pumps needs maintenance.The Hydrovar provides automatic lead/lag,

alternation when programmed in multi-control and wired via RS485 communication terminals.

TANK

Frequent demand or

small system losses determine pressure variations that may be compensated for by using a

tank. Correct selection of a diaphragm tank reduces the number of pump starts and, if it is installed near the

booster set, helps reduce the effect of water hammer, or fast acting flush valves.

The booster sets are

ready for installation of diaphragm tanks directly on the delivery manifold, and additional tanks

can be connected to the unused end of the manifold.
For peak performance, variable speed booster sets need smaller tanks compared to traditional systems.

Generally speaking, a tank with a capacity of just 20% of the nominal capacity of a single pump, expressed in gallons
per minute, is required. Example: If my pump is sized for 100 GPM, then we would size a 20 gallon (total capacity)
diaphragm tank.

Pre-charge the tank with air, 10-15 PSI below your system pressure. Charge dry tank without water pressure or before

installing in system.

Advertising