Masonry or prefabricated chimney conversion – Jotul GF 200 DV User Manual

Page 11

Advertising
background image

11

Masonry or Prefabricated Chimney
Conversion

The GF200 DV Lillehammer is approved for use with
Simpson Dura-vent Chimney Kit #934 in a masonry
chimney or a prefabricated solid fuel listed chimney.
These installation requirements must be followed:
1. In masonry chimney, a fireclay liner or listed steel

liner, must be present the entire length of the
chimney.

2. The liner must have an inside dimension of 6”

round or greater. (USE KIT #934)

3. Prefabricated chimneys must be UL 103 or ULC S-

629 listed and have a minimum INSIDE diameter
of 6 inches, (150 mm). Prefabricated chimneys
must be listed for the specific Simpson Dura-Vent
Chimney Conversion Kit. (USE KIT #931, #932, or
#933)

4. The Exhaust Restrictor plate, shipped with the

stove, must be installed according to the instruc-
tions on page 8.

WARNING:

FAILURE TO POSITION THE PARTS AND

STOVE IN ACCORDANCE WITH THESE

DIAGRAMS OR FAILURE TO USE ONLY

PARTS SPECIFICALLY APPROVED WITH

THIS APPLIANCE MAY RESULT IN

PROPERTY DAMAGE OR PERSONAL

INJURY. BE SURE TO MAINTAIN THE

PROPER CLEARANCES TO COMBUS-

TIBLES AS DEFINED IN THIS MANUAL

AND IN THE INSTRUCTIONS PROVIDED

WITH EACH SIMPSON DURA-VENT

COMPONENT.

Figure 10. Vent System through a masonry chimney
using the Simpson Dura-Vent Chimney Conversion Kit
#934. May also be used in listed prefabricated
chimneys. Drawing is for illustrative purposes only - DO
NOT VENT TWO APPLIANCES INTO A SINGLE CHIMNEY.

#991 Vertical
Termination Cap

Cap Adaptor-
included in
#934 Kit

Support/Wall
Thimble Cover -
included
in#934 Kit

Exhaust Gas

Intake Air

Use Standard
Simpson
Dura-Vent GS
Pipe from
stove to
thimble

4” Flex Pipe
not included
in kit

Figure 11. Gas Vent Height Rule: Vertical vent
termination height above roof.

Flat to 6/12

1’ 0”

0.3 M

Over 7/12 to 9/12

2’ 0”

0.6 M

Over 10/12 to 12/12

4’ 0”

1.2 M

Over 13/12 to 16/12

6’ 0”

1.8 M

Over 17/12 to 21/12

8’ 0”

2.4 M

Minimum

Height above Roof

ROOF SLOPE

2 ft.

min.

Horizontal Overhang

Vertical W

all

12

Roof Pitch

is X / 12

X

Termination

Cap

2 ft.

min.

Lowest

Discharge

Opening

2 ft.

min.

2 ft. = minimum height from

roof to lowest discharge opening

IMPORTANT NOTICE

THE USE OF AN EXISTING CHIMNEY

AS AN AIR INTAKE IS NOT COVERED

UNDER THE ANSI Z21.88-1999-CSA

2.33-M99 TEST METHODS AND RE-

SULTING ITS/WHI PRODUCT CERTIFI-

CATION. THE CODE AUTHORITY

HAVING JURISDICTION MUST BE

CONSULTED PRIOR TO PROCEEDING

WITH THIS INSTALLATION METHOD.

Advertising