Horizontal termination, 12 cl – Jotul GF 600 DV User Manual

Page 12

Advertising
background image

12

CL

Horizontal Termination

„

The horizontal termination cap must maintain a
3” clearance to any overhead combustible
projections that are 2 1/2” or less. It must also
maintain a 12” clearance from projections that
exceed 2 1/2”. See Figure 9.

„

Minimum vertical rise from the top exit position

is a 24” section vent pipe. See Fig. 10.

„

A horizontal vent run made directly off the rear
of the stove must terminate ONLY with a 36”
Snorkel Cap
.
The maximum horizontal run shall include no
more than a single 24” section of pipe. See
Figure 11.

„

The termination cap must not be recessed into the
wall or siding. Do not fill air space in wall around
termination cap with any type of insulation.

„

A minimum 11” X 11” square hole is required for
the proper pipe clearance through a wall pen-
etration. A 10” x 10” opening is suitable with use
of Simpson Dura-Vent Wall Thimble #942.

„

Any horizontal run of vent must be level or have
a 1/4” rise for every foot of run toward the
termination cap.

„

Prevent potential damage to vinyl siding with
installation of a Vinyl Siding Standoff between
the vent cap and the exterior wall.

Standard Horizontal

termination cap

(#984, #985)

Minimum vertical

rise with horizontal

termination: 24”

Maximum

horizontal with 2

ft. vertical is 12”

90° Elbow

(#990B)

Figure 10. A vertical run in a horizontal termination
must be at least 2 feet (61 cm).

Figure 11. Rear Exit Horizontal Termination.

36” Snorkel

Maximum horizontal
run into a 36” Snorkel:
24” (610 mm )

Rear Exit

Position

24 ”

610 mm

58 1/2”

(148.6 cm)
center line

with required

2ft. rise and

90° elbow