EXHAUST RESTRICTORS REQUIRED ON ALL

CO-LINEAR INSTALLATIONS.

ALWAYS MAINTAIN THE PROPER

CLEARANCES TO COMBUSTIBLES.

Co-linear Hearthmount Installation

The GF 600 DV Firelight can be installed using a
Hearthmount Co-linear Flexible Vent System,
designed for installation into a solid fuel burning
masonry fireplace. See Figures 7 and 8.

„

Refer to the vent manufacturer’s instructions for
venting components and installation details.

„

Installation of Simpson Dura-Vent Co-linear
adapter (#923GCL) directly off the rear of the
stove. (No length of pipe prior to the adaptor).

„

Use only 3” listed flexible gas vent liners may be
used in this installation.

WARNING: FAILURE TO POSITION THE PARTS AND

STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR

FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED

FOR USE WITH THIS APPLIANCE MAY RESULT IN

PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE

TO MAINTAIN THE PROPER CLEARANCES TO COMBUS-

TIBLES AS DEFINED IN THIS MANUAL AND IN THE

INSTRUCTIONS PROVIDED WITH EACH VENT COMPO-

NENT.

#991

High Wind Cap

#923GK

Top Kit

#923GCL

Co-linear

Appliance

Adaptor

Dual

3” Flex

Liners

Chimney must

be sealed with

Block-off Plate

if Air Inlet does

not extend all

the way to

terminus.

Co-linear

Exhaust Height:

Maximum - 10 ft.

(3 m)

Maximum - 35 ft.

(10.5 m)

Figure 7. Co-linear Hearthmount Vent System

IMPORTANT NOTICE:

THE USE OF AN EXISTING CHIMNEY AS

AN AIR INTAKE IS NOT COVERED

UNDER THE ANSI Z21.88-1999-CSA 2.33-

M99 TEST METHODS AND RESULTING

ITS/WHI PRODUCT CERTIFICATION. THE

CODE AUTHORITY HAVING

JURISDICTION MUST BE CONSULTED

PRIOR TO PROCEEDING WITH THIS

INSTALLATION METHOD.

Figure 6. Air Inlet Restrictor Plate installation.

Restrictor

Plate

Right Air Inlet

Rear Log Shelf

A

A

Minimum

Co-linear

Air Inlet

Height:

6 feet

(180 cm)