Gas pressure, Gas connection – Jotul GF 600 DV User Manual

Page 17

Advertising
background image

17

Leak test:

1. Mix a 50-50 solution of water and dish soap.
2. Light appliance- see lighting instructions on page

22 of this manual or on the stove’s rating plate.

3. Brush or spray all joints and connections with the

soapy water solution.

4. If bubbles appear at any connection or seam or a

gas odor is detected immediately turn gas control
knob to the OFF position.

5. Tighten or reconnect the leaking joint and retest

for any gas leaks.

Gas Pressure

It is important that the correct pressure is estab-
lished at the time of the installation. Proper gas
pressure provides a consistent flow of gas to the
appliance and is instrumental in checking for gas
leaks. The gas control valve on the stove is equipped
with pressure test points for gauge connections. The
gauge connections are located on the front of the
valve under the On/Off/Pilot- knob. See Fig. 18.
Gauge connections are identified by:
• E for inlet or supply pressure ( the amount of gas

coming to the valve.)

• A for manifold pressure (the amount of gas that

is coming out of the valve to the burner.)

ALWAYS TEST PRESSURES WITH VALVE CONTROL
KNOB SET ON HIGH.

Gas Connection

NOTE: IF THE OPTIONAL BLOWER KIT (# 129161) IS
TO BE INSTALLED ON THE STOVE AT THE TIME OF THE
INSTALLATION OR IN THE FUTURE, THE GAS SUPPLY
LINE SHOULD BE INSTALLED AS CLOSE TO THE FLOOR
AS POSSIBLE. USE OF A 90° ELBOW DIRECTLY OFF THE
VALVE TO ALLOW FOR ADEQUATE CLEARANCE FOR
THE BLOWER. See Figure 15.

The gas supply line connection is made to the

valve just inside the left rear leg. The Gas supply line
should be 3/8" or 1/2" diameter, or the appropriate
size to provide sufficient gas pressure to the valve
regardless of the input setting.

The use of Flexible Gas Appliance Connectors is

acceptable in many areas in the U.S., however,
Canadian methods vary depending on local code.

ALL INSTALLATIONS MUST COMPLY WITH LOCAL

CODE OR IN THE ABSENCE OF LOCAL CODE, MUST
COMPLY WITH THE MOST RECENT EDITION OF THE
NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54 OR
CAN-B149.

All codes require a gas shutoff valve (gas cock)

and union to be installed in the supply line and in
the same room as the appliance for servicing and
maintenance. See Figure 17.

T-handle gas cocks are required in Massachu-

setts in compliance with Code 248 CMR.

Secure all joints tightly using appropriate tools

and sealing compounds (for propane units be sure to
use compounds that are propane resistant). Turn on
gas supply and test for gas leaks using a soapy water
solution. Never use an open flame to check for
leaks.

Figure 17. Gas supply valve types and fittings.

INLET GAS PRESSURES

(inches water column)

MIN

MAX

NATURAL GAS 5.0 WC

7.0 WC

PROPANE

11.0 WC

13.5 WC

Figure 18. Inlet and Manifold pressure test points.

E

A

Control Valve

Advertising