Johnson Controls Unitary Products

TABLE 15: ELECTRIC HEAT CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTIPLIER

208

208

0.75

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 16: VOLTAGE LIMITATIONS

1

1. Utilization Range “A” in accordance with ARI Standard

110.

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

630