10 unit dimensions (rear view), 11 disconnect/blower access location, 17 utilities entry – Johnson Controls SUNLINE 2000 BQ 060 User Manual

Page 24: 18 minimum clearances, D 10 for, D 11 for, Table 18: minimum clearances

Advertising
background image

364985-XIM-B-0508

24

Johnson Controls Unitary Products

FIGURE 10 - UNIT DIMENSIONS (REAR VIEW)

FIGURE 11 - DISCONNECT/BLOWER ACCESS
LOCATION

TABLE 17: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO

1

Control Wiring

2

Side

Bottom

B

2” KO

1

Power Wiring

Side

Bottom

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

1. Opening in the bottom to the unit can be located by the

side in the insulation.

2. Do not remove the 2” knockout ring.

Disconne

ct Switch Location

and Motor Access Panel for
Unit with “Belt-Drive” Option

Control Box Access

A,B
Wiring Entry
(See Detail “B”)

Mounting Bracket for
Disconnect Switch
(Field Supplied)

Field-Supplied Disconnect
Switch Location

Blower Motor Access

Filter Access

Dot Plugs

TABLE 18: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

24”

Below Unit

1

0”

Above Unit

2

72” (For

Condenser Air Discharge)

1. Units may be installed on combustible floors made

from wood or class A, B, or C roof covering material.

2. Units must be installed outdoors. Overhanging struc-

tures or shrubs should not obstruct condenser air dis-
charge outlet.