Unit flash codes, Unit control board flash codes – Johnson Controls SUNLINE 2000 BQ 060 User Manual

Page 37

Advertising
background image

364985-XIM-B-0508

Johnson Controls Unitary Products

37

The UCB will flash the last five alarms on the LED. If
the compressor is locked out, cancel any call for cool-
ing. This will reset any compressor lock outs.

NOTE:

While the above step will reset any lockouts,
the compressor may be held off for the ASCD.
See the next step.

10. If 24 volts is present at the UCB Y1 terminal and

none of the switches are open and the compressor
is not locked out, the UCB may have the compres-
sor in an ASCD. Check the LED for an indication of
an ASCD cycle. The ASCD should time out within
5 minutes. Press and release the TEST button to
reset all ASCDs.

11. If 24 volts is present at the UCB Y1 terminal and the

compressor is not out due to a protective switch trip,
repeat trip lock out, or ASCD, the economizer termi-
nals of the UCB may be improperly wired. Check for
24 volts at the Y1 “OUT” terminal of the UCB. If 24
volts is present, trace the wiring from Y1 “OUT” for
incorrect wiring. If 24 volts is not present at the Y1
“OUT” terminal, the UCB must be replaced.

12. For units without economizers: If 24 volts is present

at the Y1 OUT terminal, check for 24 volts at the
Y1 “ECON” terminal. If 24 volts is not present,
check for loose wiring from the Y1 “OUT” terminal
to the Mate-N-Lock plug, the jumper in the Mate-N-
Lock plug, and in the wiring from the Mate-N-Lock
plug to the Y1 “ECON” terminal.

13. For units with economizers: If 24 volts is present at

the Y1 “OUT” terminal, check for 24 volts at the Y1
“ECON” terminal. If 24 volts is not present, check
for loose wiring from the Y1 “OUT” terminal to the
Mate-N-Lock plug, a poor connection between the
UCB and economizer Mate-N-Lock plugs, loose
wiring from the Mate-N-Lock plug to the econo-
mizer, back to the Mate-N-Lock plug, and from the
Mate-N-Lock plug to the Y1 “ECON” terminal. If
nothing is found, the economizer actuator may
have faulted and is failing to return the 24-volt “call”
to the Y1 “ECON” terminal even though the econo-
mizer is not providing free cooling. To test, discon-
nect the Mate-N-Locks and jumper between the
WHITE and YELLOW wires of the UCB’s Mate-N-
Lock plug. If the compressor energizes, there is a
fault in the economizer wiring or actuator.

14. The UCB can be programmed to lock out compres-

sor operation during free cooling and in low ambi-
ent conditions. These options are not enabled by
default. Local distributors can test the UCB for this
programming.

For units with factory installed economizers, the
UCB is programmed to lock out compressor opera-
tion when the LAS set point is reached.

For units without factory installed or with field
installed economizers, the UCB allows compressor
operation all the time. This programming can be
checked or changed by the local distributor.

15. If none of the above correct the error, replace the

UCB.

UNIT FLASH CODES

Various flash codes are utilized by the unit control
board (UCB) to aid in troubleshooting. Flash codes are
distinguished by the short on and off cycle used
(approximately 200ms on and 200ms off). To show
normal operation, the control board flashes a 1 second
on, 1 second off “heartbeat” during normal operation.
This is to verify that the UCB is functioning correctly.
Do not confuse this with an error flash code. To prevent
confusion, a 1-flash, flash code is not used.

Current alarms are flashed on the UCB LED. Pressing
and releasing the ALARMS button on the UCB can
check the alarm history. The UCB will cycle through the
last five (5) alarms, most recent to oldest, separating
each alarm flash code by approximately 2 seconds.

In some cases, it may be necessary to “zero” the
ASCD for the compressors in order to perform trouble-
shooting. To reset all ASCDs for one cycle, press and
release the UCB TEST button once.

TABLE 32: UNIT CONTROL BOARD FLASH CODES

Flash Code

Description

On Steady

Control Failure - Replace Control

Heart Beat

Normal Operation

1 Flash

Not Applicable

2 Flashes

Control waiting ASCD

1

1. These flash codes do not represent alarms.

3 Flashes

HPS1 - Compressor Lock out

5 Flashes

LPS1 - Compressor Lock out

7 Flashes

FS1 - Compressor Lock out

9 Flashes

Ignition Control Locked Out/
Ignition Control Failure / Limit Switch Trip /
No Jumper Plug in Heat Section

10 Flashes

Compressors Locked Out On Low

Outdoor Air Temperature

1

11 Flashes

Compressors Locked Out Because the

Economizer Is Using Free Cooling

1

13 Flashes

Compressor Held Off Due To Low Voltage

1

14 Flashes

EEPROM Storage Failure (Control Failure)

OFF

No Power or Control Failure

Advertising
This manual is related to the following products: