Minimum position adjustment, Enthalpy set point adjustment, Indoor air quality – Johnson Controls SUNLINE 2000 BQ 060 User Manual

Page 12: Power exhaust damper setpoint (with, Or without power exhaust)

Advertising
background image

364985-XIM-B-0508

12

Johnson Controls Unitary Products

MINIMUM POSITION ADJUSTMENT

With thermostat set to indoor fan on position, or termi-
nals “R” to “G” energized, turn the Minimum Position
Adjusting screw (located on the damper control mod-
ule) counterclockwise until the desired minimum
damper position has been attained.

ENTHALPY SET POINT ADJUSTMENT

The enthalpy setpoint may now be set by selecting the
desired setpoint shown in the Enthalpy Setpoint Adjust-
ment Figure 4. Adjust as follows:

For a single enthalpy operation carefully turn the
setpoint adjusting screw (found on the damper
control module) to the “A”, “B”, “C” or “D” setting
corresponding to the lettered curve of the Enthalpy
Setpoint Adjustment Figure 4.

For a dual enthalpy operation, carefully turn the
setpoint adjusting screw fully clockwise past the
“D” setting.

POWER EXHAUST DAMPER SETPOINT (WITH OR WITH-
OUT POWER EXHAUST)

With no power exhaust option, adjust the Exhaust
Air Adjustment Screw fully clockwise.

With power exhaust option, each building pressur-
ization requirement will be different. The point at
which the power exhaust comes on is determined
by the economizer damper position (Percent
Open). The Exhaust Air Adjustment Screw should
be set at the Percent Open of the economizer
damper at which the power exhaust is needed. It
can be set from 0 to 100% damper open.

INDOOR AIR QUALITY

Indoor air quality (indoor sensor input): Terminal AQ
accepts a +2 to +10 Vdc signal with respect to the
(AQ1) terminal. When the signal is below it's setpoint,
the actuator is allowed to modulate normally in accor-
dance with the enthalpy and mixed air sensor inputs.
When the AQ signal exceeds it's setpoint setting and
there is no call for free cooling, the actuator is propor-
tionately modulated from the 2 to 10 Vdc signal, with 2
Vdc corresponding to full closed and 10 Vdc corre-
sponding to full open. When there is no call for free
cooling, the damper position is limited by the IAQ Max
damper position setting. When the signal exceeds it's
setpoint (Demand Control Ventilation Setpoint) setting
and there is a call for free cooling, the actuator modu-
lates from the minimum position to the full open posi-
tion based on the highest call from either the mixed air
sensor input or the AQ voltage input.

Optional CO

2

Space Sensor Kit Part #

2AQ04700324

Optional CO

2

Unit Sensor Kit Part # 2AQ04700424

Replace the economizer access panel.