Clearance to combustible materials, Service clearance, Insulation blankets – State Industries ULTRA FORCE 101 User Manual

Page 13: Breathing hazard - carbon monoxide gas

Advertising
background image

13

There is a risk in using fuel burning appliances such as gas water

heaters in rooms, garages or other areas where gasoline, other

flammable liquids or engine driven equipment or vehicles are

stored, operated or repaired. Flammable vapors are heavy and

travel along the floor and may be ignited by the water heater’s

igniter or main burner flames causing fire or explosion.
Flammable items, pressurized containers or any other potential

fire hazardous articles must never be placed on or adjacent to

the water heater.
clearance to combustible materials
The water heaters covered in this manual are approved for

installation on combustible flooring. The clearance to combustible

and non combustible construction materials is 0 inches on the

back and sides of the water heater. These water heaters are also

approved for installation in an alcove.
note: Adequate clearance for servicing should be maintained

on all installations. See Service Clearance below.

TOP VIEW

0

0

0

ALCOVE

FRONT VIEW

CLEARANCES TO COMBUSTIBLE

AND NON COMBUSTIBLE

CONSTRUCTION MATERIALS

WATER

HEATER

FRONT

TOP COVER

FRONT

figure 7

serVice clearance
A service clearance of 24 inches (61 cm) should be maintained

from serviceable parts such as the T&P valve, control system

components, gas valve, clean out opening, drain valve, the vent

connection (exhaust elbow) and the condensate drain. Leave as

much room as possible above the water heater and near the

exhaust elbow for this reason. See Figure 9 on page 17.
intake air and Vent pipe clearances
The minimum clearance from combustible materials for the vent

(exhaust) and intake air piping shall be 0 inches. Vent or intake

air piping passing through a combustible wall or ceiling must be

a continuous run (no joints).

extended Vent terminations

The water heaters covered by this manual can be installed using

3 inch pipe for the intake air and/or vent piping up to a maximum

of 50 equivalent feet (15.2 m). The intake air and/or vent piping

can be extended up to 120 equivalent feet (36.5 m) by installing

4 inch pipe. See the Venting requirements on page 24.
The water heater ships from the factory with two (2) 3 inch

terminations that are 45° PVC elbows with a debris screen

installed. When 4 inch intake air or vent pipe is installed, factory

supplied 4 inch terminations must be used.
Contact your local distributor or call the parts department phone

number listed on the back cover of this manual to order 4 inch

termination(s).

optional concentric terminations

The water heaters covered in this manual can be installed in a

Direct Vent configuration using an optional concentric termination.

See Concentric Termination installation on page 30.

hard water

Where hard water conditions exist, water softening or the

threshold type of water treatment is recommended. This will

protect the dishwashers, coffee urns, water heaters, water

piping and other equipment. See maintenance on page 64 for

sediment and lime scale removal procedures.

circulation pumps

A circulating pump is used when a system requires a circulating

loop or there is a storage tank used in conjunction with the water

heater. See the Water Piping Diagrams beginning on page 71

for installation location of circulating pumps.
See Circulation Pump Wiring Diagrams on page 70 for

electrical hookup information. install in accordance with the

current edition of the National Electrical Code, NFPA 70 or the

Canadian Electrical Code, CSA C22.1.
All-bronze circulating pumps are recommended for used with

commercial water heaters.
Some circulating pumps are manufactured with sealed bearings

and do not require further lubrication. Some circulating pumps

must be periodically oiled. refer to the pump manufacturer’s

instructions for lubrication requirements.

insulation blankets

Do not obstruct water heater air intake

with insulating blanket.
Gas and carbon monoxide detectors

are available.
Install water heater in accordance with

the instruction manual.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Breathing Hazard - Carbon Monoxide Gas

insulation blankets are available to the general public for external

use on gas water heaters but are not necessary with these

products. The purpose of an insulation blanket is to reduce the

standby heat loss encountered with storage tank heaters. The

water heaters covered by this manual meet or exceed the Energy

Policy Act standards with respect to insulation and standby heat

loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this

heater, you should follow these instructions. See the Features

and Components section of this manual for identification of

components mentioned below. Failure to follow these instructions

can restrict the air flow required for proper combustion, potentially

resulting in fire, asphyxiation, serious personal injury or death.

do not apply insulation to the top of the water heater, as this

will interfere with safe operation of the blower assembly.

do not cover the control system LCD on top of the water heater.

do not cover the Temperature-Pressure relief Valve.

do not cover the instruction manual. keep it on the side of the

water heater or nearby for future reference.

do obtain new warning and instruction labels from the

manufacturer for placement on the blanket directly over the

existing labels.

do inspect the insulation blanket frequently to make certain it

does not sag, thereby obstructing combustion air flow.

Advertising
This manual is related to the following products: