outline, connection diagram for external cabling, internal wiring diagram, and written instruction
for installation.




1.4 FINAL

SUBMITTALS


Upon delivery of the UPS system the following submittals shall be included:

A. A complete set of installation drawings showing all the information stated in section 1.3.

B. An installation and users manual showing safe and correct operation of all UPS functions.

1.5

QUALIFICATIONS & QUALITY ASSURANCE

A. Manufacturer’s

Certification: The manufacturer shall specialize in manufacturing of on-line,

double conversion three phase UPS modules specified in this document with a minimum of
twenty years documented experience, and with a nationwide first party service organization.
The manufacturer shall be ISO 9001 certified and shall design to internationally accepted
standards.

B. Factory Testing: Prior to shipment the manufacturer shall complete a documented test

procedure to test all functions of the UPS module and batteries (via a discharge test), when
supplied by the UPS manufacturer, and guarantee compliance with the specification. The
factory test shall be performed in the presence of the customer providing the manufacturer
receives adequate prior notice. The manufacturer shall provide a copy of the test report upon
request.

C. Materials and Assemblies: All materials and parts comprising the UPS shall be new, of

current manufacture, and shall not have been in prior service, except as required during factory
testing. All active electronic devices shall be solid state and not exceed the manufacturer’s
recommended tolerances for temperature or current to ensure maximum reliability. All
semiconductor devices shall be sealed. All relays shall be provided with dust covers. The
manufacturer shall conduct inspections on incoming parts, modular assemblies, and final
products.

1.6

DELIVERY, STORAGE, AND HANDLING


A. All products shall be packaged in a manner to prevent penetration by debris and to allow safe

delivery by all modes of ground transportation and air transportation where specified.

B. Prior to shipping all products shall be inspected at the factory for damage.

C. Equipment shall be protected against extreme temperature and humidity and shall be stored in

a conditioned or protected environment.


D. Equipment containing batteries shall not be stored for a period exceeding three months without

powering up the equipment for a period of eight hours to recharge the batteries.

1.7 ENVIRONMENTAL

REQUIREMENTS


The UPS shall operate under the following environmental conditions:

A. Temperature:

APC – MGE Galaxy 5000 Specification (60Hz)

2

Effective: June 1, 2008 REV X0 JJG