2.2 SYSTEM

DESCRIPTION


A. UPS Design Requirements

1. Output Power Continuous Rating: The continuous output power rating of the UPS shall

be [ ] kVA at a 0.9 lagging power factor.


Galaxy 5000 available: Choose 40, 50, 60, 80, 100, 130kVA

2. Input Voltage: 480 VAC – 15% / +10%, 3 phase, 3 wire “grounded wye” configuration

plus ground.


3. Output voltage: 480 VAC 3 phase, 3 plus ground

4. Battery Autonomy: The UPS shall be capable of operating at full load for [ ] minutes at

0.9 PF output at a temperature of 25°C on battery power.

5. Battery Type: Valve regulated sealed lead acid (VRLA)

B. AC Input Characteristics

1. Voltage: 480VAC, – 15% / +10%, 3 phase, 3 wire “grounded wye” configuration plus

ground.

2. Frequency: 60 Hz ±5%

3. Power Factor: > .98 lagging

4. Total Harmonic Distortion: less than 5% at full load

5. Inrush Current: less than nominal input current for less than one cycle

6. Input Surge Protection: The UPS is equipped to withstand surges per IEC 1004/ANSI

C62.41


C. AC Output Characteristics

1. Voltage: 480VAC , – /+ 1% steady-state variation phase to phase voltage VAC , 3 phase,

3 wire plus ground

2. Frequency: 60 Hz +1% (or selectable up to 4%); 60 Hz + 0.1% when free running

3. Voltage Regulation:

+ 1.0% for balanced load
+ 1.75 for 50% unbalanced load
+ 2.5% for 100% unbalanced load


4. Voltage

Distortion: Maximum 2% total (THD) and 1% any single harmonic on 100% linear

loads.


5. Voltage Transient (Step Load) Response: + 3% for 50% step load change

+ 5% for 100% step load change

APC – MGE Galaxy 5000 Specification (60Hz)