The graphic display shall assist the user by providing step by step help in the

user's language.

o

LED mimic diagram

o

The mimic diagram shall enable display of installation parameters, configuration,

operating status and alarms and indication of operator instructions for switching
operations (e.g. bypass).

o

It shall be possible to display the following measurements:

ƒ inverter output phase-to-phase voltages;
ƒ inverter output currents;
ƒ inverter output frequency;
ƒ voltage across battery bank;
ƒ battery charge or discharge current;
ƒ rectifier/charger

input phase-to-phase voltages;

ƒ rectifier/charger input currents;
ƒ active and apparent power;
ƒ power factor of the load;
ƒ battery

temperature.

ƒ display of status conditions and events

o

It shall be possible to display the following indications:

ƒ load on battery power;
ƒ load on UPS;
ƒ load on automatic bypass;
ƒ general

alarm;

ƒ battery

fault;

ƒ remaining battery backup time;
ƒ low battery warning;
ƒ bypass AC source outside tolerances;

o

Additional information shall be provided in view of accelerating servicing of the

system.

o

Log of time-stamped events

ƒ This function shall store in memory and make available, for automatic or

manually initiated recall, time-stamped logs of all important status
changes, faults and malfunctions, complete with an analysis and display
of troubleshooting procedures. It shall be possible to time stamp and
store at least 2 000 events.


B. Front Panel LCD Display: The UPS control panel shall provide a back-lit, color graphic

display with choice of over 15 operating languages for indication of UPS status, metering,
battery status, alarm/event log, and advanced operational features. The display provides
access to:

ƒ

Mimic diagram indicating UPS power flow

ƒ

Measurements, status indications and events

ƒ

Personalization menu protected by a password, used to make specific settings

ƒ

Event log with time stamping

ƒ

Access to all measurements


System Parameters Monitored: The visual display will display the following system
parameters based on true RMS metering:

Measurements:

ƒ

Input voltage (Ph-Ph)

ƒ

Input current per phase

APC – MGE Galaxy 5000 Specification (60Hz)

8