+ 1% for loss or return of AC input power or

manual transfer at full load

6. Voltage

Recovery

Time: Return to within 1% of nominal value within 16.67 milliseconds

(one cycle)


7. Phase Angle Displacement: 120° + 1° for balanced load; 120° + 3° for 100% unbalanced

load


8. Non-Linear Load Capability: Output voltage total harmonic distortion shall be less than

3% when connected to a 100% non-linear load with a crest factor not to exceed 3%.


9. Slew Rate: 1 Hz/second maximum (or selectable up to 2.0 Hz/sec)

10. Power Factor: 0.9 at the rated volt-amperes (VA)

11. Inverter Overload Capability: 125% of rated load for 10 minutes

150% of rated load for 1 minute

12. Bypass Overload Capability: > 212% for one cycle; > 150% for 1 minute

D. Battery

1. Battery Voltage: 356 VDC minimum before cutoff; 432 VDC nominal; 490 VDC

equalization voltage


2. Maximum DC Current: Maximum DC current at cutoff voltage will be [ ] A.

2.3

MODES OF OPERATION

The UPS module shall be designed to operate as a double conversion, on-line reverse transfer
system in the following modes.

A. Normal: The inverter shall continuously supply power to the critical load. The PFC rectifier shall

derive power from the utility AC source and supply DC power to the inverter while
simultaneously float charging the battery.

B. Emergency: Upon failure of the utility AC power source, the critical load shall be supplied by

the inverter, which, without any interruption, shall obtain its power from the battery.

C. Recharge: Upon restoration of the utility AC power source (prior to complete battery discharge),

the PFC rectifier shall power the inverter and simultaneously recharge the battery.

D. Bypass Mode: The static bypass transfer switch shall be used to transfer the load to the

bypass without interruption to the critical power load. This shall be accomplished by turning the
inverter off. Automatic re-transfer or forward transfer of the load shall be accomplished by
turning the inverter on.


2.4 COMPONENT

DESCRIPTION

A. PFC Rectifier and Battery Charger

APC – MGE Galaxy 5000 Specification (60Hz)

5

Effective: June 1, 2008 REV X0 JJG