Setting the Fixed Voltage Level

Your Sunways Solar Inverter is equipped

with a precise MPP control. If less than

200 watt are injected, the control of the

energy unit concerned operates at a fixed

voltage level. That prevents unnecessary

MPP searching. To minimise adjustment

losses during fixed voltage operation, the

fixed voltage level of each energy unit of

the Solar Inverter can be set separately.

The optimum fixed voltage level depends

on your PV generator model.

The fixed voltage can be set with the slide

switch «S100» on the control circuit board.

Ex works, the switch is set to «420V».

To set a fixed voltage of 540 V, slide the

switch to the «540V» position.

Fixed voltage

level

420 V

540 V

No-load voltage

PV generator at 25 °C

630 V

> 630 V

«420 V» position

«540 V» position

Illustr.: Slide switch «S100» for setting the

fixed voltage level