140

Errors 007 to 009

· Overheating

Your Solar Inverter is designed for an

ambient temperature of up to +40° C.

If the maximum temperature of the heat

sink is exceeded, the injection will stop.

When the heat sink temperature has

dropped, the Solar Inverter will automa-

tically restart. If the upper heat sink over-

heats, for example, «error 009» will be

flagged.

Errors 010 to 012

· Grid undervoltage 1-phase

Your Solar Inverter continuously monitors

the voltage level of the injection phase.

If it drops below the minimum admissible

limit value, the Solar Inverter will stop the

injection and only restart when the voltage

value rises above the minimum admissible

limit value. If the voltage of L1 drops

below 160 V, the Solar Inverter can no

longer be supplied, and the display will

switch off. If there is a grid undervoltage

on phase L3, for example, «error 012» will

be flagged.

Errors 013 to 015

· Grid overvoltage 1-phase

Your Solar Inverter continuously monitors

the voltage level of the injection phase.

If it rises above the maximum admissible

limit value, the Solar Inverter will stop the

injection and only restart when the voltage

value drops below the maximum admissi-

ble limit value. If there is a grid overvolta-

ge on phase L2, for example, «error 014»

will be flagged.

Error 016

· Grid undervoltage 3-phase

Your Solar Inverter is equipped with an

intrinsically safe 3-phase grid monitoring

system that complies with E DIN VDE

0126-1-1. The voltage level of phases L1,

L2, and L3 is continuously monitored.

If it drops below the minimum admissible

limit value, the Solar Inverter will stop the

injection and only restart when the voltage

value rises above the minimum admissible

limit value.