UNIT CONTROL BOARD OPTION SETUP

OPTION BYTE SETUP

• Enter the Option Setup mode by pushing the OPTION

SETUP / STORE button, and holding it for at least 2
seconds.

• The green status LED (Option Byte) will be turned on

and the red status LED (Heat Delay) is turned off.

• The 8, 4, 2 and 1 LEDs will then show the status of the

4 labeled options ((8) Fan Off at Heat Start, (4) Low
Ambient Lockout
, (2) Free Cooling Lockout, and (1)
Lead / Lag)
.

• Press the UP or Down button to change the LED status

to correspond to the desired Option Setup.

• To save the current displayed value, push the OPTION

SETUP / STORE button and hold it for at least 2
seconds. When the value is saved, the green LED will
flash a few times and then normal display will resume.

NOTE:

While in either Setup mode, if no buttons are
pushed for 60 seconds, the display will revert
to its normal display, exiting the Option Setup
mode. When saving, the control board only
saves the parameters for the currently dis-
played mode (Option Byte or Heat Delay).

HEAT DELAY SETUP

•Enter the Option Setup mode by pushing the OPTION

SETUP / STORE button, and holding it for at least 2
seconds.

•The green status LED (Option Byte) will be turned on

and the red status LED (Heat Delay) is turned off.

•Press the COMM SETUP / SELECT button to toggle into

the Heat Delay Setup, the green LED will turn off and
the red LED for Heat Delay will turn on.

• The 8, 4, 2 and 1 LEDs will then show the status of the

Heat Delay, (See Table 25). Press the UP or Down
button to change the LED status to correspond to the
desired Heat Delay Value.

• To save the current displayed value, push the OPTION

SETUP / STORE button and hold it for at least 2
seconds. When the value is saved, the red LED will
flash a few times and then normal display will resume.

NOTE:

While in either Setup mode, if no buttons are
pushed for 60 seconds, the display will revert
to its normal display, exiting the Option Setup
mode. When saving, the control board only
saves the parameters for the currently dis-
played mode (Option Byte or Heat Delay).

TABLE 25: HEAT DELAY

Heat

Fan On

Delay

Heat

Fan Off

Delay

Red

LED 8

Red

LED 4

Red

LED 2

Red

LED 1

60

180

On

On

On

On

60

90

On

On

On

Off

60

60

On

On

Off

On

60

30

On

On

Off

Off

45

180

On

Off

On

On

45

90

On

Off

On

Off

45

60

On

Off

Off

On

45

30

On

Off

Off

Off

30

180

Off

On

On

On

30

90

Off

On

On

Off

30

60

Off

On

Off

On

30

30

Off

On

Off

Off

0

60

Off

Off

On

On

0

30

Off

Off

On

Off

0

10

Off

Off

Off

On

Non-std

Non-std

Off

Off

Off

Off