1 acoustic requirements, 2 airflow requirements, 3 temperature requirements – SSI America ERP2U User Manual

Page 10: Acoustic requirements, Airflow requirements, Temperature requirements, Figure 2 system airflow impedance, Table 1 recommended acoustic sound power levels

Advertising
background image

SSI

ERP2U Power Supply Design Guide, V2.31

- 10 -

4.1 Acoustic

Requirements

STATUS

Recommended

It is recommended the power supplies have a variable speed fan based on temperature and loading conditions.
There are three different acoustic sound power levels defined at different ambient temperatures and loading
conditions.

Table 1 Recommended Acoustic Sound Power Levels

Idle

Typical

Max

Ambient

Temperature

28ºC 28ºC 45ºC

%

Loading

30% 60% 100%

Sound Power (BA)

5.2

5.6

6.1

4.2 Airflow

Requirements

STATUS

Recommended

The air shall exit the power supply on the AC inlet face. The power supply shall meet all requirements with the
below system airflow impedance presented to the power supplies airflow path.

Figure 2 System Airflow Impedance

System Flow Impedance - 2U

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0

5

10

15

20

Power Supply Airflow (CFM)

S

yst

em

P

ressur

e

(

in

H

2

O)

4.3 Temperature

Requirements

STATUS

Recommended