3 . Securely fasten the support brackets to the burner box

sides with (4) #14 x 5/8” Hex washer head, type B tapping

screws . (Hardware package is supplied) .

Upright

Main Body

Side

#14 x 3/4"

Type "B"

Washer Hex

Head Sheet Metal

Screws (4 Req'd)

Ventilation Air

The following notes are intended to give general guidance .

For detailed recommendations, refer to the applicable

code(s) in the country of destination .

Proper ventilation is critical for optimum performance . The

ideal method of ventilating open-top equipment is the use

of a properly designed canopy that should extend six inches

(152 mm), beyond all sides of the appliance(s) and six feet, six

inches (1981mm) above the floor .

A strong exhaust will create a vacuum in the room . For an

exhaust vent to work properly, replacement air must be

equal to the amount of exhausted .

All gas burners and pilots need sufficient air to operate . Large

objects should not be placed in front of the appliance(s) that

would obstruct the flow of air into the front .

Statutory Regulations

The installation of this appliance must be carried out by

a competent person and in accordance with the relevant

regulations, codes of practice and the related publications of

the country of destination .

The installation must conform to the National Fuel Gas Code

ANSI Z223 .1, or latest edition, NFPA No .54 - latest edition/or

local code to assure safe and efficient operation . In Canada,

the installation must comply with CSA B149 .1 and local

codes .

Gas Connection

The local gas authority should be consulted at the

installation planning stage in order to establish the

availability of an adequate supply of gas and to ensure

that the meter is adequate for the required flow rate . The

pipe work from the meter to the appliances must be an

appropriate size .

All fixed (non-mobile) appliances MUST be fitted with

an accessible Upstream gas shut off valve as a means of

isolating the appliance for emergency shut off and for

servicing . A union or similar means of disconnection must be

provided between the gas-cock and the appliance .

A manually operable valve must be fitted to the gas supply

to the kitchen to enable it to be isolated in an emergency .

Wherever practical, this shall be located either outside the

kitchen or near to an exit in a readily accessible position .

Where it is not practical to do this, an automatic isolation

valve system shall be fitted which can be operated from a

readily accessible position near to the exit .

In locations where the manual isolation valve is fitted or the

automatic system can be reset a notice MUST be posted

stating:

“ALL DOWNSTREAM BURNER AND PILOT VALVES MUST

BE TURNED OFF PRIOR TO ATTEMPTING TO RESTORE THE

SUPPLY . AFTER EXTENDED SHUT OFF, PURGE BEFORE

RESTORING GAS .”

Installation Notes

Before assembly and connection check gas supply .

A . The type of gas for which the unit is equipped is stamped

on the data plate located behind the lower front panel .

Connect a unit stamped “NAT” only to natural gas;

connect one stamped “PRO” only to propane gas .

INSTALLATION Continued