Siemens RS-485 User Manual

Page 10

Advertising
background image

10/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Address

Data

type

Access

Parameter

Value range

Default

value

0x0300

word [13]

R / O

Device data

0x0300

char SWVersion [11+1]

Software version

0x0306

char VDNNr [13+1]

VdN number

Address

Data

type

Access

Parameter

Value range

Default

value

0x0400

float

R / O

TEMP

Actual value E3 (unfiltered)

0x0500

word

R / W

REM

Activation remote operation

0...2 *

0

0x0501

word

R / W

ROFF

Controller OFF in REMOTE
SETPOINT

0...1 **

0

0x0502

float

R / W

RHYS1

Switch-on threshold REMOTE

0...-1999

HYS1

0x0504

float

R / W

RHYS2

Switch-off threshold bottom
REMOTE

0...RHYS3

HYS2

0x0506

float

R / W

RHYS3

Switch-off threshold top REMOTE

0...9999

HYS3

0x0508

float

R / W

SPR

Setpoint REMOTE

SPL...SPH

SP1

0x050A

word

R / W

RK1

Burner control remote operation

0...1

0

0x050B

word

R / W

RK2

Relay K2 remote operation

0...1

0

0x050C

word

R / W

RK3

Relay K3 remote operation

0...1

0

0x050D

word

R / W

RK6

Relay LK remote operation

0...1

0

0x050E

word

R / W

RSTEP

Step control remote operation

-100...100

0

0x050F

float

R / W

RY

Positioning output remote
operation

0...100

0

*

0 = local

**

1 = controller OFF

1 = remote setpoint
2 = fully remote

Device data

Remote operation