Siemens RS-485 User Manual

Page 11

Advertising
background image

11/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Address

Data type

Access

Parameter

0x0200

word

R / O

Outputs and states

B15 B14 B13 B12 B11 B10

B9

B8

B7

B6

B5

B4

B3

B2

B1

B0

B8

Hysteresis limitation

B0

Output 1 off

(for remote operation)

B1

Output 3 off

B9

Management system off

B2

Output 2 off

(for remote operation)

B3

Output 4 off

B10

Self-optimization active

B11

Second setpoint active

B12

Measured value range crossing input 1

B13

Measured value range crossing input 2

B14

Measured value range crossing input 3

B15

Reserved

0x0201

word

R / O

Binary signal and hardware identification

B15 B14 B13 B12 B11 B10

B9

B8

B7

B6

B5

B4

B3

B2

B1

B0

B15

Reserved

B0

Operating mode 2-stage active

B14

Interface present

B1

Manual operation active

B13

Analog output present

B2

Binary input 1 closed

B3

Binary input 2 closed

B4

Thermostat function active

B5

First controller output active

B6

Second controller output active

B7

Limit comparator active

Device state