Siemens RS-485 User Manual

Page 7

Advertising
background image

7/14

Siemens Building Technologies

CC1A7865.1en

HVAC Products

31.10.2002

Reading n words

This function is used to read n words from a certain address.

Slave address

Function 0x03

or 0x04

Address of the

first word

Number of

words

(max. 12)

Checksum

CRC16

1 byte

1 byte

2 bytes

2 bytes

2 bytes

Slave address

Function 0x03

or 0x04

Number of
bytes read

Word value(s)

Checksum

CRC16

1 byte

1 byte

1 byte

x byte(s)

2 bytes

Reading the 2 setpoints of the controller
Word address = 0x0008 (setpoint SP1)

Data query:

0B

03

00

08

00

04

CRC16

Reply:

0B

03

08

0000

42C8

0000

4316

CRC16

Setpoint 1 (100)

Setpoint 2 (150)

Writing 1 word

With the “Wordwriting” function, the data blocks for instruction and reply are identical.

Slave address

Function 0x06

Word address

Word value

Checksum

CRC16

1 byte

1 byte

2 bytes

2 bytes

2 bytes

Slave address

Function 0x06

Word address

Word value

Checksum

CRC16

1 byte

1 byte

2 bytes

2 bytes

2 bytes

Write limit value limit comparator 1 (AL1) (= 275)
Word address = 0x000C

Instruction: (write the first part of the value)

0B

06

00

0C

80

00

CRC16

Reply (like instruction):

0B

06

00

0C

80

00

CRC16

Instruction: (write the second part of the value)

0B

06

00

0D

43

89

CRC16

Reply (like instruction):

0B

06

00

0D

43

89

CRC16

Data query

Reply

Example

Instruction

Reply

Example